Wire Size Calculator
A 30 A continuous load on a 240 V single-phase circuit 200 ft from the panel needs 6 AWG copper (75 °C column, 3% drop): the load counts as 37.5 A (125% of 30 A), which 8 AWG copper would carry, but over 200 ft that loses too much voltage, so voltage drop sets the size. At 6 AWG the drop is 5.89 V (2.46%). Enter the load in amps or watts, the voltage, one-way length, copper or aluminum, the insulation temperature column and the drop you allow (3% by default): the calculator picks the smallest size that passes NEC Table 310.16 ampacity, the NEC 240.4(D) limits on small conductors and your voltage drop limit, and says which one decided it. It is an estimate, not a substitute for a licensed electrician or your local code.
Updated Runs in your browser: nothing you enter is uploadedHow this tool works
Needs 30 A × 125% = 37.5 A of ampacity (75 °C column) and at most 7.2 V of drop (3% of 240 V).
6 AWG copper
Voltage drop sets the size: a smaller conductor has enough ampacity but loses more than the limit over this run.
- Governing constraint
- Voltage drop
- Ampacity needed
- 37.5 A (125% of load)
- Ampacity of 6 AWG, 75 °C
- 65 A
- Smallest for ampacity
- 8 AWG copper
- Smallest for voltage drop
- 6 AWG copper
- Voltage drop at this size
- 5.89 V (2.46%)
- Voltage at the load
- 234.11 V of 240 V
- Longest run within the limit
- 244 ft
- Conductor resistance
- 0.491 Ω per 1000 ft
- Size if terminals are 60 °C
- 6 AWG copper
Most equipment rated 100 A or less is evaluated with the 60 °C column unless it is marked 75 °C (NEC 110.14(C)(1)). You chose the 75 °C column: unless the breaker and device are marked for it, use 6 AWG copper or larger.
An estimate, not a design. This is not a substitute for a licensed electrician. Wire also has to suit the breaker, the terminals, the conduit, the ambient temperature and the number of conductors, and the code adopted where you live may differ from the NEC. Have a licensed electrician or your inspector check any real installation.
Ampacity: NEC Table 310.16 (2023)
| Size | Cu 60 °C | Cu 75 °C | Cu 90 °C | Al 60 °C | Al 75 °C | Al 90 °C |
|---|---|---|---|---|---|---|
| 14 AWG | 15 | 20 | 25 | n/a | n/a | n/a |
| 12 AWG | 20 | 25 | 30 | 15 | 20 | 25 |
| 10 AWG | 30 | 35 | 40 | 25 | 30 | 35 |
| 8 AWG | 40 | 50 | 55 | 30 | 40 | 45 |
| 6 AWG | 55 | 65 | 75 | 40 | 50 | 55 |
| 4 AWG | 70 | 85 | 95 | 55 | 65 | 75 |
| 3 AWG | 85 | 100 | 115 | 65 | 75 | 85 |
| 2 AWG | 95 | 115 | 130 | 75 | 90 | 100 |
| 1 AWG | 110 | 130 | 145 | 85 | 100 | 115 |
| 1/0 AWG | 125 | 150 | 170 | 100 | 120 | 135 |
| 2/0 AWG | 145 | 175 | 195 | 115 | 135 | 150 |
| 3/0 AWG | 165 | 200 | 225 | 130 | 155 | 175 |
| 4/0 AWG | 195 | 230 | 260 | 150 | 180 | 205 |
| 250 kcmil | 215 | 255 | 290 | 170 | 205 | 230 |
| 300 kcmil | 240 | 285 | 320 | 195 | 230 | 260 |
| 350 kcmil | 260 | 310 | 350 | 210 | 250 | 280 |
| 400 kcmil | 280 | 335 | 380 | 225 | 270 | 305 |
| 500 kcmil | 320 | 380 | 430 | 260 | 310 | 350 |
Small-conductor limits: NEC 240.4(D)
| Size | Copper | Aluminum |
|---|---|---|
| 14 AWG | 15 A | n/a |
| 12 AWG | 20 A | 15 A |
| 10 AWG | 30 A | 25 A |
Smallest copper size by load: 100 ft, 240 V single-phase, 75 °C, 3% drop
| Load | Not continuous | Continuous |
|---|---|---|
| 15 A | 12 AWG | 12 AWG |
| 20 A | 10 AWG | 10 AWG |
| 30 A | 8 AWG | 8 AWG |
| 40 A | 8 AWG | 8 AWG |
| 50 A | 6 AWG | 6 AWG |
| 60 A | 6 AWG | 4 AWG |
How to choose a wire size
- Find the load current. Use the amps on the nameplate, or divide watts by volts (single-phase) or by √3 × volts (three-phase). 7,200 W ÷ 240 V = 30 A.
- Add 25% for a continuous load. A load that runs 3 hours or more is counted at 125%: NEC 210.19(A)(1) for branch circuits and 215.2(A)(1) for feeders. 30 A becomes 37.5 A. A non-continuous load counts at 100%.
- Pick the smallest size with enough ampacity. Read Table 310.16 in the column for the lowest-rated part of the circuit (the 60 °C column for most equipment of 100 A or less, unless it is marked 75 °C). The example needs 8 AWG copper.
- Check the small-conductor limits. For 14, 12 and 10 AWG copper and 12 and 10 AWG aluminum, NEC 240.4(D) caps the breaker at 15, 20 and 30 A for copper and 15 and 25 A for aluminum, whatever the table says. A 25 A load therefore cannot use 12 AWG copper even though its 75 °C column reads 25 A.
- Check the voltage drop. Drop = 2 × length × amps × resistance ÷ 1000 (√3 in place of 2 for three-phase), compared with your limit, 3% of the voltage by default. The example needs 6 AWG copper.
- Use the larger of the answers. The size must pass all three tests, so take the biggest result: 6 AWG copper for the example. Then have an electrician check conduit fill, bundling and ambient derating, the terminals and local code.
Frequently asked questions
- What size wire do I need for a 20 amp, 30 amp or 50 amp circuit?
- On a short run (10 ft, not continuous, 60 °C terminals) the calculator gives 12 AWG copper for 20 A, 10 AWG for 30 A and 6 AWG for 50 A, following Table 310.16 and the 240.4(D) limits. A longer run or a continuous load can push the size up one or two steps: the same 30 A load over 200 ft as a continuous load is 6 AWG in the example above.
- Why does a continuous load need 125%?
- A load expected to run for 3 hours or more is a continuous load. NEC 210.19(A)(1) (branch circuits) and 215.2(A)(1) (feeders) require the conductors to carry 125% of it, so the breaker is not held at its limit for hours. In the example 30 A counts as 37.5 A. Without the 125% option the example needs 10 AWG copper for ampacity, instead of 8 AWG copper. The voltage drop is still worked on the actual 30 A.
- Which temperature column of Table 310.16 should I use?
- The one that matches the lowest-rated part of the circuit: the wire insulation, the breaker terminal or the device terminal. NEC 110.14(C)(1) says equipment rated 100 A or less (or marked for 14 to 1 AWG conductors) is evaluated at 60 °C unless it is marked for 75 °C, and equipment over 100 A at 75 °C. A 90 °C wire such as THHN can start from the 90 °C column for derating (heat, bundling), but the final ampacity still cannot exceed the terminal column.
- What is NEC 240.4(D)?
- It limits the overcurrent protection of small conductors: 14 AWG copper to 15 A, 12 AWG copper to 20 A, 10 AWG copper to 30 A, 12 AWG aluminum to 15 A and 10 AWG aluminum to 25 A (aluminum includes copper-clad aluminum). It is why 12 AWG copper is not used on a 25 A breaker even though Table 310.16 lists 25 A at 75 °C: for a 25 A non-continuous load the calculator picks 10 AWG copper and shows "NEC 240.4(D) limit" as the governing constraint.
- How much voltage drop is allowed?
- The NEC sets no hard limit for ordinary circuits. Informational notes to 210.19(A) and 215.2(A) recommend no more than 3% on a branch circuit or feeder and 5% overall. Informational notes are advice, not requirements, but equipment instructions and some local codes do set limits. The default here is 3% and you can change it: at 5% the example needs 8 AWG copper instead of 6 AWG copper.
- How do I size wire from watts?
- Change "Load in" to watts. Single-phase amps = watts ÷ volts; three-phase amps = watts ÷ (√3 × volts); the calculator assumes a power factor of 1. 7,200 W on 240 V is 30 A and gives 6 AWG copper in the example. 10,000 W on 208 V three-phase is 27.76 A and, over 100 ft with a 3% limit, 10 AWG copper.
- Is aluminum wire sized differently from copper?
- Yes. For the same size it carries less current (Table 310.16 lists lower values) and has more resistance, so it normally goes up one or two sizes: the example run is 4 AWG aluminum instead of 6 AWG copper. Aluminum is listed from 12 AWG, and it needs terminals and connectors marked for it.
- What are the limits of this calculator?
- It uses Table 310.16 (30 °C ambient, no more than three current-carrying conductors) and does not apply ambient temperature correction, adjustment for more than three conductors in a conduit, conduit fill, motor or air conditioner rules, grounding conductor sizing, or the rounding of the breaker up to the next standard size. It does not cover wire in free air, underground or aluminum service-entrance cable, and it stops at 500 kcmil: larger loads need parallel conductors and an engineer or electrician.
- Can I use this to wire my house or EV charger myself?
- It can show what size to expect and help you talk to the electrician, but it is not a substitute for a licensed electrician, a permit or an inspection. Local code may add to or change the NEC, and an EV charger or a range has its own rules. Have a licensed electrician check any real installation.
How it works
The calculator takes the load in amps (or converts watts: watts ÷ volts, or watts ÷ (√3 × volts) for three-phase, at a power factor of 1) and multiplies it by 1.25 for a continuous load (NEC 210.19(A)(1), 215.2(A)(1)). For each size of the chosen metal, from 14 AWG (12 AWG for aluminum) up to 500 kcmil, it checks three things and picks the first size that passes all of them. 1) Ampacity: the value in NEC 2023 Table 310.16 for the temperature column you chose is at least the required amps. 2) NEC 240.4(D): for 14, 12 and 10 AWG copper and 12 and 10 AWG aluminum, the ampacity is capped at 15, 20, 30, 15 and 25 A. 3) Voltage drop: 2 × L × I × R ÷ 1000 for single-phase, √3 × L × I × R ÷ 1000 for three-phase, with L the one-way length in feet, I the actual load current (not the 125% figure) and R the DC resistance in ohms per 1000 ft at 75 °C from NEC Chapter 9, Table 8 (the same table and formula as the voltage drop calculator), at most your limit as a percent of the voltage. The "governing constraint" is the test that asked for the largest size: voltage drop if it needed a bigger size than ampacity, the 240.4(D) limit if the table value alone would have allowed a smaller size, and ampacity otherwise. Terminal temperature: under NEC 110.14(C)(1) most equipment of 100 A or less is evaluated at 60 °C unless marked 75 °C, and larger equipment at 75 °C, so for loads up to 100 A the tool also shows the size you would need if the terminals are 60 °C. Simplifications: ambient temperature correction (Table 310.15(B)(1)) and adjustment for more than three current-carrying conductors (310.15(C)(1)) are not applied; neither are conduit fill, motor and air conditioner rules (Articles 430 and 440), the standard sizes of breakers (240.6) or the equipment grounding conductor (Table 250.122). Reactance is ignored in the voltage drop and a three-phase load is assumed balanced. This is an estimate for planning, not a design or a code check, and it is not a substitute for a licensed electrician. The code your area has adopted, and its edition, decides what is allowed. Everything runs in your browser.
Sources
- NFPA 70, National Electrical Code (2023), Table 310.16 Allowable Ampacities of Insulated Conductors (values unchanged since the 2014 edition; cross-checked against several published reproductions, as the NFPA text itself is behind a free-access viewer)
- NFPA 70, 240.4(D) Small Conductors (14 AWG Cu 15 A, 12 AWG Cu 20 A, 10 AWG Cu 30 A, 12 AWG Al 15 A, 10 AWG Al 25 A)
- NFPA 70, 210.19(A)(1) and 215.2(A)(1) (125% of the continuous load) and 110.14(C) (temperature limitations at terminations)
- NFPA 70, Chapter 9, Table 8 Conductor Properties (resistance used for voltage drop, as in the voltage drop calculator)
More free tools
- Voltage Drop CalculatorEstimate voltage drop in volts and percent for copper or aluminum wire, single or three phase, and find the smallest AWG size that stays within 3% or 5%.
- Conduit Fill CalculatorCheck how many wires fit in EMT, rigid, PVC or flexible conduit under NEC Chapter 9: fill percent, pass or fail, and the most of one wire size that fits.
- Generator Size CalculatorAdd up running watts and the largest starting surge for the appliances you want to power, and get a generator size with amps at 120 and 240 volts.
- Electricity Cost CalculatorFind what an appliance or a list of appliances costs to run: kWh and cost per day, month and year from watts (or amps and volts), hours and your rate.
- Feet and Inches CalculatorAdd, subtract, multiply and divide lengths like 5' 7 3/8" with exact fractions, rounded to 1/16 inch, plus decimal feet, mm and cm and a tape view.
- Board Foot CalculatorBoard feet for a whole cut list: pieces × thickness × width × length, 4/4 to 16/4 hardwood or nominal 2×4s, with waste and the cost at your price.