Voltage Drop Calculator
12 AWG copper carrying 15 A over 100 ft one way on a 120 V single-phase circuit drops 5.94 V (4.95%), leaving 114.06 V at the load. That is over the 3% the NEC informational notes suggest for a branch circuit but within 5%; 8 AWG copper keeps it to 3% or less. Pick copper or aluminum, the wire size, single or three phase, the length, current and source voltage: the calculator shows the drop in volts and percent, the voltage at the load and the smallest size for 3% and for 5%. It is an estimate from published resistance values, not a design: ampacity (NEC 310.16) is a separate requirement, and a licensed electrician or your inspector decides what your installation needs.
Updated Runs in your browser: nothing you enter is uploadedHow this tool works
2 × 100 ft × 15 A × 1.98 Ω/1000 ft ÷ 1000 = 5.94 V
5.94 V drop (4.95%)
Over 3% but within 5%. The 5% is meant for feeder and branch circuit together, so a branch circuit this long leaves little for the feeder.
- Voltage drop
- 5.94 V
- Drop as % of source
- 4.95%
- Voltage at the load
- 114.06 V of 120 V
- Conductor
- 12 AWG copper, 1.98 Ω per 1000 ft
- Smallest for 3% or less
- 8 AWG copper (2.33 V, 1.95%)
- Smallest for 5% or less
- 12 AWG copper (5.94 V, 4.95%)
An estimate, not a design. This checks voltage drop only, using the resistance values in NEC Chapter 9, Table 8. It does not check ampacity (NEC 310.16), overcurrent protection or local code, and the 3% and 5% figures come from informational notes, which are recommendations. Have a licensed electrician check any real installation.
Wire resistance used: NEC Chapter 9, Table 8
| Size | Copper (Ω per 1000 ft) | Aluminum (Ω per 1000 ft) |
|---|---|---|
| 14 AWG | 3.14 | 5.17 |
| 12 AWG | 1.98 | 3.25 |
| 10 AWG | 1.24 | 2.04 |
| 8 AWG | 0.778 | 1.28 |
| 6 AWG | 0.491 | 0.808 |
| 4 AWG | 0.308 | 0.508 |
| 3 AWG | 0.245 | 0.403 |
| 2 AWG | 0.194 | 0.319 |
| 1 AWG | 0.154 | 0.253 |
| 1/0 AWG | 0.122 | 0.201 |
| 2/0 AWG | 0.0967 | 0.159 |
| 3/0 AWG | 0.0766 | 0.126 |
| 4/0 AWG | 0.0608 | 0.1 |
| 250 kcmil | 0.0515 | 0.0847 |
| 300 kcmil | 0.0429 | 0.0707 |
| 350 kcmil | 0.0367 | 0.0605 |
| 400 kcmil | 0.0321 | 0.0529 |
| 500 kcmil | 0.0258 | 0.0424 |
Longest one-way run for 3% drop, copper, 120 V single-phase
| Size | 10 A | 15 A | 20 A | 30 A | 50 A |
|---|---|---|---|---|---|
| 14 AWG | 57 ft | 38 ft | 28 ft | 19 ft | 11 ft |
| 12 AWG | 90 ft | 60 ft | 45 ft | 30 ft | 18 ft |
| 10 AWG | 145 ft | 96 ft | 72 ft | 48 ft | 29 ft |
| 8 AWG | 231 ft | 154 ft | 115 ft | 77 ft | 46 ft |
| 6 AWG | 366 ft | 244 ft | 183 ft | 122 ft | 73 ft |
| 4 AWG | 584 ft | 389 ft | 292 ft | 194 ft | 116 ft |
| 2 AWG | 927 ft | 618 ft | 463 ft | 309 ft | 185 ft |
| 1/0 AWG | 1,475 ft | 983 ft | 737 ft | 491 ft | 295 ft |
| 4/0 AWG | 2,960 ft | 1,973 ft | 1,480 ft | 986 ft | 592 ft |
Longest one-way run for 3% drop, copper, 240 V single-phase
| Size | 10 A | 15 A | 20 A | 30 A | 50 A |
|---|---|---|---|---|---|
| 14 AWG | 114 ft | 76 ft | 57 ft | 38 ft | 22 ft |
| 12 AWG | 181 ft | 121 ft | 90 ft | 60 ft | 36 ft |
| 10 AWG | 290 ft | 193 ft | 145 ft | 96 ft | 58 ft |
| 8 AWG | 462 ft | 308 ft | 231 ft | 154 ft | 92 ft |
| 6 AWG | 733 ft | 488 ft | 366 ft | 244 ft | 146 ft |
| 4 AWG | 1,168 ft | 779 ft | 584 ft | 389 ft | 233 ft |
| 2 AWG | 1,855 ft | 1,237 ft | 927 ft | 618 ft | 371 ft |
| 1/0 AWG | 2,950 ft | 1,967 ft | 1,475 ft | 983 ft | 590 ft |
| 4/0 AWG | 5,921 ft | 3,947 ft | 2,960 ft | 1,973 ft | 1,184 ft |
How to calculate voltage drop by hand
- Find the resistance of the wire. Look up the size in NEC Chapter 9, Table 8. 12 AWG uncoated copper is 1.98 ohms per 1000 ft at 75 °C.
- Measure the one-way length and the load current. Length is the run from the source to the load, one way, in feet (meters × 3.2808). Current is the load in amps, not the breaker rating, unless you want the worst case.
- Multiply. Single-phase: 2 × length × current × resistance ÷ 1000, because current goes out and back. For the example, 2 × 100 × 15 × 1.98 ÷ 1000 = 5.94 V. Three-phase uses √3 (about 1.732) in place of 2.
- Turn it into a percent. Divide the drop by the source voltage and multiply by 100: 5.94 ÷ 120 × 100 = 4.95%.
- Compare with 3% and 5%. The informational notes suggest 3% or less on a branch circuit or feeder and 5% or less overall. Try the next size up until it passes: for the example that is 8 AWG copper.
- Check ampacity separately. A size that passes the drop test still has to carry the current safely: check NEC 310.16 and the breaker and terminal ratings, or ask an electrician.
Frequently asked questions
- What is the voltage drop formula?
- Single-phase: VD = 2 × L × I × R ÷ 1000. Three-phase: VD = √3 × L × I × R ÷ 1000. L is the one-way length in feet, I the current in amps and R the wire's resistance in ohms per 1000 ft. For 12 AWG copper, 100 ft and 15 A on 120 V that is 2 × 100 ft × 15 A × 1.98 Ω/1000 ft ÷ 1000 = 5.94 V, or 4.95% of 120 V.
- How much voltage drop is acceptable?
- The NEC does not set a hard limit for ordinary circuits. Informational Note No. 4 to 210.19(A) says branch-circuit conductors sized so the drop at the farthest outlet is no more than 3%, and the total for feeder and branch circuit together no more than 5%, give reasonable efficiency of operation; an informational note to 215.2(A) says the same for feeders (its number differs between code editions). Informational notes are advice, not requirements, but other rules, equipment instructions and some local codes do set limits.
- What wire size keeps 100 ft of a 20 A, 120 V circuit under 3%?
- Copper: 8 AWG; aluminum: 6 AWG. For 5% the smallest copper size is 10 AWG. These come from the drop alone: the conductor also needs enough ampacity for a 20 A breaker (12 AWG copper at least), whatever the drop.
- Why is the formula 2 × length?
- Current flows from the source to the load and back, so a single-phase circuit has two conductors of the length you measure, and both lose voltage. In a balanced three-phase circuit the currents partly cancel, so the total loss is √3 (1.732) times the one-way figure rather than 2. That is why a three-phase run of the same size, length and current loses about 13% less voltage in volts.
- Does aluminum have more voltage drop than copper?
- Yes, about 1.6 times as much for the same size: 12 AWG aluminum in the example drops 9.75 V (8.13%) against 5.94 V for copper. Aluminum is normally sized one or two steps larger for the same job, and it needs terminals rated for it.
- Does a higher voltage reduce the percent drop?
- Yes. The volts lost depend on the current, not the source voltage, so the same load on 240 V has half the percent drop of 120 V: the example circuit drops 5.94 V either way but that is 2.48% of 240 V. (A 240 V load draws half the current for the same watts, which halves the drop in volts again.)
- How do I calculate three-phase voltage drop?
- Use √3 (1.732) in place of 2. For 8 AWG copper, 150 ft and 30 A on 208 V three-phase the drop is 6.06 V, 2.92% of 208 V. This assumes a balanced load and uses the voltage between phases.
- Can I enter the length in meters?
- Yes: choose meters and the calculator converts at 1 m = 3.2808 ft before using the formula. 30 m of 12 AWG copper at 15 A and 120 V is 98.43 ft and a drop of 5.85 V. The resistance values are per 1000 ft.
- Is this enough to size my wire?
- No. It estimates the drop only. Wire also has to carry the current within its ampacity (NEC 310.16 and the rules on temperature ratings, conduit fill, bundling and ambient temperature), match the breaker, and meet the code your area has adopted. Have a licensed electrician check any design before you build it, especially anything on a panel, a feeder or a motor.
How it works
Voltage drop is current × resistance, counted over the whole conductor path. Single-phase: VD = 2 × L × I × R ÷ 1000; three-phase: VD = √3 × L × I × R ÷ 1000, with L the one-way length in feet, I in amps and R in ohms per 1000 ft. R is the DC resistance of uncoated copper or aluminum at 75 °C from NEC Chapter 9, Table 8, using the stranded-conductor rows (solid 14, 12 and 10 AWG wire reads slightly lower, so the estimate errs high for it); the full list is in the table above. The percent is the drop divided by the source voltage you pick. The smallest size is the first in the list from 14 AWG to 500 kcmil whose drop is 3% (or 5%) or less of that voltage, using the same length and current. Simplifications: it uses DC resistance, so it ignores the inductive reactance that matters for large conductors in steel conduit and at a poor power factor (NEC Chapter 9 Table 9 gives AC values); real wire is usually cooler than 75 °C and so loses slightly less; the load is treated as one lump at the end of the run with a steady current; a three-phase load is assumed balanced; and starting current of motors is not considered. This is an estimate for planning, not a design or a code check. It does not check ampacity (NEC 310.16), overcurrent protection, conduit fill or the code in force where you live, and the 3% and 5% figures come from informational notes, which are recommendations. A licensed electrician or your inspector decides what is right for an installation. Everything runs in your browser.
Sources
- NFPA 70, National Electrical Code, Chapter 9, Table 8 Conductor Properties (DC resistance at 75 °C); values cross-checked against published reproductions of the table
- NFPA 70, 210.19(A) Informational Note No. 4 (3% at the farthest outlet, 5% total for feeder and branch circuit) and the matching informational note to 215.2(A) for feeders
- NFPA 70, Table 310.16 Allowable ampacities of insulated conductors (a separate requirement from voltage drop)
- EC&M, How to Use Chapter 9 in Your Next Design (Table 8 and voltage drop)
More free tools
- Conduit Fill CalculatorCheck how many wires fit in EMT, rigid, PVC or flexible conduit under NEC Chapter 9: fill percent, pass or fail, and the most of one wire size that fits.
- Generator Size CalculatorAdd up running watts and the largest starting surge for the appliances you want to power, and get a generator size with amps at 120 and 240 volts.
- Wire Size CalculatorFind the smallest copper or aluminum wire size for a load: checks NEC ampacity, the 240.4(D) small-wire limits and voltage drop, and shows which governs.
- Unit ConverterConvert length, area, volume, weight and temperature with exact factors, plus cubic yards, tons and bags for gravel, soil, sand and concrete.
- Feet and Inches CalculatorAdd, subtract, multiply and divide lengths like 5' 7 3/8" with exact fractions, rounded to 1/16 inch, plus decimal feet, mm and cm and a tape view.
- Electricity Cost CalculatorFind what an appliance or a list of appliances costs to run: kWh and cost per day, month and year from watts (or amps and volts), hours and your rate.