Electrical Box Fill Calculator
4 conductors of 12 AWG, 2 grounds and 1 receptacle in a 3 × 2 × 3-1/2 in device box need 15.75 cu in of the 18.00 cu in the box offers: it passes with 2.25 cu in to spare, room for 1 more 12 AWG conductor. Pick a standard box or enter the volume marked on yours, then count the conductors by size and add the grounds, clamps, support fittings and devices: the calculator applies the NEC 314.16(B) volume allowances (12 AWG is 2.25 cu in, 14 AWG 2.00 cu in) and shows required against available volume, pass or fail, and how many more conductors fit. It is an aid built on published table values: the inspector and the NEC edition your jurisdiction has adopted govern.
Updated Runs in your browser: nothing you enter is uploadedHow this tool works
Pass: 15.75 of 18.00 cu in used
The count needs 15.75 cu in and the 3 × 2 × 3-1/2 in device box has 18.00 cu in, leaving 2.25 cu in: room for 1 more 12 AWG conductor.
| Item | Allowances | Each (cu in) | Total (cu in) | More that fit |
|---|---|---|---|---|
| 4 × 12 AWG | 4 | 2.25 | 9.00 | 1 |
| 2 equipment grounding conductors, 12 AWG | 1 | 2.25 | 2.25 | - |
| 1 yoke with devices (2 allowances each, 12 AWG) | 2 | 2.25 | 4.50 | - |
- Box
- 3 × 2 × 3-1/2 in device box
- Conductors counted
- 4
- Largest conductor
- 12 AWG, 2.25 cu in each
- Required volume
- 15.75 cu in
- Box volume
- 18.00 cu in
- Volume to spare
- 2.25 cu in
- Fill
- 87.5%
- Each yoke counts two allowances for one device or a combination device on a single strap. A device wider than a single 2 in device box, such as a double-wide switch, needs two allowances for each gang it occupies.
An aid, not an inspection.
- Volumes come from NEC Table 314.16(A) and Table 314.16(B) as reproduced by published sources, not from the NFPA text. Some box volumes are only partly confirmed: see "Sources and checks" below.
- The inspector and the NEC edition your authority having jurisdiction has adopted govern. The grounding rule here is the 2020 and 2023 wording; earlier editions count all grounds once.
- Use the volume marked on the box when it has one. Boxes with barriers, conduit bodies, and junction and pull boxes (314.28) are not covered.
Volume allowance per conductor: NEC Table 314.16(B)
| Conductor size | Allowance (cu in) | Most that fill an empty 18.00 cu in box |
|---|---|---|
| 18 AWG | 1.50 | 12 |
| 16 AWG | 1.75 | 10 |
| 14 AWG | 2.00 | 9 |
| 12 AWG | 2.25 | 8 |
| 10 AWG | 2.50 | 7 |
| 8 AWG | 3.00 | 6 |
| 6 AWG | 5.00 | 3 |
How each item is counted: NEC 314.16(B)(1) to (5)
| Item | How it counts | Allowances | Volume at 12 AWG (cu in) |
|---|---|---|---|
| Conductor that ends or is spliced in the box, or runs through | Once for each, by its own size | 1 | 2.25 |
| Unbroken loop of 12 in or more | Counted twice, by its own size | 2 | 4.50 |
| Jumper or conductor that never leaves the box | Not counted | 0 | 0.00 |
| Internal cable clamps (one or more) | One allowance for all, largest conductor in the box | 1 | 2.25 |
| Support fitting (fixture stud, hickey) | One allowance for each, largest conductor in the box | 1 | 2.25 |
| Yoke or strap with one or more devices | Two allowances for each, largest conductor connected to the device | 2 | 4.50 |
| Equipment grounding conductors, up to 4 | One allowance for all, largest grounding conductor | 1 | 2.25 |
| Each grounding conductor beyond 4 | One quarter of an allowance each, largest grounding conductor | 0.25 | 0.56 |
Standard box volumes and the most conductors of one size: NEC Table 314.16(A)
| Box | Volume (cu in) | 18 AWG | 16 AWG | 14 AWG | 12 AWG | 10 AWG | 8 AWG | 6 AWG |
|---|---|---|---|---|---|---|---|---|
| 4 × 1-1/4 in round or octagonal | 12.50 | 8 | 7 | 6 | 5 | 5 | 4 | 2 |
| 4 × 1-1/2 in round or octagonal | 15.50 | 10 | 8 | 7 | 6 | 6 | 5 | 3 |
| 4 × 2-1/8 in round or octagonal | 21.50 | 14 | 12 | 10 | 9 | 8 | 7 | 4 |
| 4 × 1-1/4 in square | 18.00 | 12 | 10 | 9 | 8 | 7 | 6 | 3 |
| 4 × 1-1/2 in square | 21.00 | 14 | 12 | 10 | 9 | 8 | 7 | 4 |
| 4 × 2-1/8 in square | 30.30 | 20 | 17 | 15 | 13 | 12 | 10 | 6 |
| 4-11/16 × 1-1/4 in square | 25.50 | 17 | 14 | 12 | 11 | 10 | 8 | 5 |
| 4-11/16 × 1-1/2 in square | 29.50 | 19 | 16 | 14 | 13 | 11 | 9 | 5 |
| 4-11/16 × 2-1/8 in square | 42.00 | 28 | 24 | 21 | 18 | 16 | 14 | 8 |
| 3 × 2 × 1-1/2 in device box | 7.50 | 5 | 4 | 3 | 3 | 3 | 2 | 1 |
| 3 × 2 × 2 in device box | 10.00 | 6 | 5 | 5 | 4 | 4 | 3 | 2 |
| 3 × 2 × 2-1/4 in device box | 10.50 | 7 | 6 | 5 | 4 | 4 | 3 | 2 |
| 3 × 2 × 2-1/2 in device box | 12.50 | 8 | 7 | 6 | 5 | 5 | 4 | 2 |
| 3 × 2 × 2-3/4 in device box | 14.00 | 9 | 8 | 7 | 6 | 5 | 4 | 2 |
| 3 × 2 × 3-1/2 in device box | 18.00 | 12 | 10 | 9 | 8 | 7 | 6 | 3 |
| 4 × 2-1/8 × 1-1/2 in device box | 10.30 | 6 | 5 | 5 | 4 | 4 | 3 | 2 |
| 4 × 2-1/8 × 1-7/8 in device box | 13.00 | 8 | 7 | 6 | 5 | 5 | 4 | 2 |
| 4 × 2-1/8 × 2-1/8 in device box | 14.50 | 9 | 8 | 7 | 6 | 5 | 4 | 2 |
| 3-3/4 × 2 × 2-1/2 in masonry box | 14.00 | 9 | 8 | 7 | 6 | 5 | 4 | 2 |
| 3-3/4 × 2 × 3-1/2 in masonry box | 21.00 | 14 | 12 | 10 | 9 | 8 | 7 | 4 |
Sources and checks
| Item | Status | Detail |
|---|---|---|
| Table 314.16(B) allowances, 18 to 6 AWG | Confirmed | 1.50, 1.75, 2.00, 2.25, 2.50, 3.00 and 5.00 cu in agree with the Electrical Contractor magazine series "Box-Fill Calculations, Understanding NEC Article 314" and with manufacturer code guides. |
| Two allowances for a yoke, one for clamps, one per support fitting | Confirmed | Stated the same way in the Electrical Contractor series and in the manufacturer guides consulted. |
| One EGC allowance for up to four, plus one-quarter for each beyond four | Partly confirmed | The 2020 NEC introduced this rule, based on the largest grounding conductor, as described in the Leviton 2020 code-change summary and the Electrical Contractor 2023 change series. The 2017 NEC and earlier count all grounding conductors once. The 2023 wording and the treatment of bonding jumpers were not checked against NFPA 70 itself. |
| Round, octagonal and 4 in square boxes: 12.5, 15.5, 21.5, 18.0, 21.0 and 30.3 cu in | Confirmed | Agree with Table 314.16(A) as reproduced in the Electrical Contractor series. |
| 4-11/16 in square, 1-1/2 in deep: 29.5 cu in; 1-1/4 in deep: 25.5 cu in | Confirmed | Agree with the Electrical Contractor series and a manufacturer catalog PDF of the table. |
| 3 × 2 in device box, 2-1/4 in deep: 10.5 cu in | Confirmed | Agrees with a manufacturer catalog PDF reproducing Table 314.16(A). |
| 3 × 2 in device box, 2 in deep: 10.0 cu in | Partly confirmed | Appears in secondary code discussion of the table; no printed reproduction was found to confirm it. |
| Other device, masonry and 4-11/16 in square box volumes | Partly confirmed | Not matched to a printed reproduction here. Check them against Table 314.16(A) or the volume marked on your box. |
| Boxes not listed (FS, FD, handy, gangable, plastic) | Not confirmed | Not included. Enter the volume marked on the box instead. |
How to calculate electrical box fill
- Count the conductors. Count every conductor that starts outside the box and ends or is spliced in it, and every conductor that runs through. In the example that is 4 conductors of 12 AWG, each 2.25 cu in from Table 314.16(B): 4 × 2.25 = 9.00 cu in. An unbroken loop of 12 in or more counts twice, and a jumper that stays inside the box is not counted.
- Add the grounds. All the equipment grounding conductors together count as one allowance of the largest one, up to four of them: 2 grounds of 12 AWG add 2.25 cu in. Each ground beyond four adds a quarter allowance (3.38 cu in for six).
- Add clamps, fittings and devices. Internal cable clamps take one allowance in total, each support fitting one, and each yoke with devices two, all at the size of the largest conductor involved. One receptacle: 2 × 2.25 = 4.50 cu in.
- Compare with the box volume. 9.00 + 2.25 + 4.50 = 15.75 cu in. The 3 × 2 × 3-1/2 in device box has 18.00 cu in, so the fill passes with 2.25 cu in to spare.
- If it fails. Use a deeper or larger box, or take out a conductor. The same count in a 3 × 2 × 2-1/2 in device box (12.50 cu in) is over by 3.25 cu in; the smallest standard box in this list that fits it is the 4 × 1-1/4 in square.
Frequently asked questions
- How do you calculate box fill?
- Add up the volume allowance of every conductor, grounding conductor, clamp, fitting and device in the box (NEC 314.16(B)) and compare the total with the box volume. For the example: 9.00 + 2.25 + 4.50 = 15.75 cu in against 18.00 cu in available.
- How many wires can go in an electrical box?
- It depends on the box volume and the wire size. An empty 3 × 2 × 3-1/2 in device box (18.00 cu in) holds 8 conductors of 12 AWG at 2.25 cu in each, or 9 of 14 AWG at 2.00 cu in. Devices, grounds and clamps use some of that room, so a box with a receptacle holds fewer.
- What is the volume allowance for each wire size?
- Table 314.16(B) gives 18 AWG 1.50 cu in, 16 AWG 1.75 cu in, 14 AWG 2.00 cu in, 12 AWG 2.25 cu in, 10 AWG 2.50 cu in, 8 AWG 3.00 cu in, 6 AWG 5.00 cu in. A conductor is counted by its own size; clamps, fittings and devices are counted at the size of the largest conductor involved.
- How do you count equipment grounding conductors?
- All the grounding conductors (bare or insulated) that enter the box count as one allowance at the size of the largest one, up to four. Under the 2020 and 2023 NEC each one beyond four adds a quarter of an allowance, so six 12 AWG grounds count as 1.5 allowances, 3.38 cu in. Earlier editions counted any number of grounds once. A separate isolated ground set under 250.146(D) is counted as a set of its own. Pigtails that stay inside the box are not counted as conductors entering it.
- How do you count a receptacle or switch?
- Each yoke or strap that holds one or more devices counts as two conductors, at the size of the largest conductor connected to it. A duplex receptacle is one yoke, so with 12 AWG wire it takes 4.50 cu in. A device wider than a single 2 in device box counts two allowances for each gang it occupies.
- Do cable clamps count?
- Only clamps inside the box, factory or field made. One or more of them count as a single allowance of the largest conductor in the box, 2.25 cu in in the example; adding them takes the example from 15.75 to 18.00 cu in. Connectors that clamp from outside the box do not count.
- How is a looped wire counted?
- A conductor that runs through the box in one unbroken piece at least twice as long as the free length required by 300.14 (so 12 in or more) is counted twice. Two 12 AWG loops need 9.00 cu in, where two cut conductors would need 4.50. A shorter unbroken run counts once.
- Which box volume should I use?
- Use the volume marked on the box if it has one: it can be larger than the table value. If it is not marked, use the minimum volume from Table 314.16(A) for its size and shape. This tool lists common metal boxes; for plastic, FS, FD or gangable boxes enter the volume marked on the box.
- Does 10 AWG or larger wire change the count?
- Yes. Larger wire takes more room: 10 AWG is 2.50 cu in against 2.25 for 12 AWG and 2.00 for 14 AWG. One larger wire also raises the allowance for the clamps, fittings and devices, which are counted at the size of the largest conductor involved.
- Is the answer an official determination?
- No. This is an aid that applies the 314.16 counting rules to published table values, which could not be checked against the NFPA text (see "Sources and checks"). The inspector and the NEC edition adopted where you work govern, and rules differ for boxes with barriers, conduit bodies and the junction and pull boxes sized under 314.28.
- Is anything I enter stored or sent?
- No. The calculation runs in your browser. Box sizes, wire sizes and counts are not stored or sent anywhere. The site records only that the tool was used, never the values.
How it works
Each conductor row is counted once (twice for an unbroken loop of 12 in or more) and multiplied by its Table 314.16(B) allowance. Equipment grounding conductors count as one allowance of the largest grounding conductor, plus a quarter allowance for each beyond four (the 2020 and 2023 NEC wording; earlier editions count all of them once), and a separate isolated set is counted the same way. Internal clamps count once in total and each support fitting once, both at the size of the largest conductor in the box. Each yoke counts twice, at the size of the largest conductor connected to the devices (the largest in the box unless you choose a size). The sum is the required volume. It passes when it does not exceed the box volume (the Table 314.16(A) minimum, or the volume you enter from the box marking). "More that fit" divides the spare volume by the conductor's allowance and rounds down. Not covered: conductors that never leave the box (they count nothing, so leave them out), short luminaire wires, boxes with barriers or listed fittings, conduit bodies, junction and pull boxes (314.28), and the extra allowances for devices wider than one gang. This is an estimate, not a design or an inspection: confirm every value against the NEC edition your authority having jurisdiction has adopted. The documents each value was checked against are listed under "Sources and checks".
Sources
- NFPA 70, National Electrical Code, Article 314 and Tables 314.16(A) and 314.16(B)
- Electrical Contractor: Box-Fill Calculations, Understanding NEC Article 314, Part II
- Electrical Contractor: Box-Fill Calculations, Understanding NEC Article 314, Part VI
- Electrical Contractor: Exploring Chapter 3 in 2023 NEC changes, Part 9
- Leviton, Box Fill Calculation Revised: volume allowance for EGCs and equipment bonding jumpers (2020 NEC change)
More free tools
- Conduit Fill CalculatorCheck how many wires fit in EMT, rigid, PVC or flexible conduit under NEC Chapter 9: fill percent, pass or fail, and the most of one wire size that fits.
- Wire Size CalculatorFind the smallest copper or aluminum wire size for a load: checks NEC ampacity, the 240.4(D) small-wire limits and voltage drop, and shows which governs.
- Voltage Drop CalculatorSingle-phase and 3-phase voltage drop for copper or aluminum wire: volts and percent lost, voltage at the load, and the smallest AWG size within 3% or 5%.
- Ohm's Law CalculatorEnter any two of voltage, current, resistance and power to get the other two, with SI prefixes. Plus series/parallel, LED resistor and voltage divider.
- Voltage Divider CalculatorResistor divider output voltage from Vin, R1 and R2, or the R1 and R2 for a target Vout, with E12/E24/E96 values, load effect, current and power.
- Feet and Inches CalculatorAdd, subtract, multiply and divide lengths like 5' 7 3/8" with exact fractions, rounded to 1/16 inch, plus decimal feet, mm and cm and a tape view.