Garage Heater Size Calculator: How Many BTU/h Do I Need?
A 24 × 24 ft two-car garage with 8 ft ceilings (4,608 cu ft) and average insulation needs about 24,515 BTU/h of heat to stay 40°F above the outdoor temperature (for example 60°F inside when it is 20°F outside): 4,608 cu ft × 40°F × 0.133. A gas unit heater that is 82% efficient needs 29,896 BTU/h of input, so a 30,000 BTU/h size covers it on propane or natural gas (0.33 gal/h of propane at full fire). An electric heater would be 7.18 kW, which draws 29.9 A at 240 V and needs a 40 A breaker. Enter your own size, ceiling height, insulation and temperature rise. This is the volume × temperature rise × factor estimate that heater guides use, not a heat-loss calculation, so treat it as a starting point.
Figures based on the sources listed belowUpdated How we calculate
24,515 BTU/h.
24,515 BTU/h
- Garage volume: 4,608 cu ft (576 sq ft × 8 ft)
- Heat to deliver: 24,515 BTU/h (4,608 cu ft × 40°F rise × 0.133 factor, average insulation)
- Gas heater input (propane or natural gas): 29,896 BTU/h input at 82% efficiency; the same BTU/h burns on propane or natural gas
- Smallest common unit heater size: 30,000 BTU/h input (Modine Hot Dawg sizes: 30,000, 45,000, 60,000, 75,000, 100,000, 125,000)
- Propane burned at full fire: 0.33 gal/h (29,896 BTU/h ÷ 91,452 BTU per gal)
- Natural gas burned at full fire: 29 cu ft/h (29,896 BTU/h ÷ 1,036 BTU per cu ft)
- Electric heater: 7,185 W (7.18 kW): resistance heat is about 100% efficient, 3,412 BTU/h per kW
- Current at 240 V: 29.9 A (7,185 W ÷ 240 V)
- Circuit breaker (125% of the load): 40 A breaker (29.9 A × 1.25 = 37.4 A, next standard size); an electrician sets the wire and breaker
- Mr. Heater square-foot rule, same garage: 23,040 BTU/h (576 sq ft × 40 BTU/h per sq ft); a sq-ft rule ignores ceiling height and temperature rise
- Cross-check: room heat loss method: 12,026 BTU/h by U × area × ΔT for walls 2,217, ceiling 1,115, door 5,376 and air leakage 3,318, assuming R-13 walls with drywall, R-19 ceiling, uninsulated metal door, 1 air change per hour. The volume method is 104% higher
Shopping list
- Garage door insulation kit
- Garage door bottom seal
- Carbon monoxide detector
- Digital thermostat, 240 V
- Tape measure (25 ft)
Your project
- Garage length × garage width: 24 × 24 ft
- Ceiling height: 8 ft
- Desired temperature rise: 40 °F
- Insulation level: Average: R-13 walls, some attic insulation
- Garage door: One double door (16 × 7 ft)
- Gas heater efficiency: 82%: power-vented unit heater (typical)
Also pick up
- Garage door insulation kit
- Garage door bottom seal
- Carbon monoxide detector
- Digital thermostat, 240 V
- Tape measure (25 ft)
Reopen this calculation: /calculators/garage-heater-size/?s=eyJyb29tIjp7Imxlbmd0aEZ0IjoyNCwid2lkdGhGdCI6MjR9LCJkZWR1Y3Rpb25zIjpbXSwid2FzdGVQY3QiOjAuMSwicGFyYW1zIjp7ImNlaWxpbmdGdCI6OCwicmlzZUYiOjQwLCJpbnN1bGF0aW9uIjoxLCJnYXJhZ2VEb29yIjoyLCJnYXNFZmZpY2llbmN5Ijo4Mn19
Show diagram
Saved projects
No saved projects yet.
Insulation factors, and the volume method against a heat-loss check, for a 24 × 24 ft garage
| Insulation level | Factor | Volume method | Heat-loss cross-check | Ratio |
|---|---|---|---|---|
| Poor | 0.173 | 31,887 BTU/h | 31,534.246 BTU/h | 1 × |
| Average | 0.133 | 24,515 BTU/h | 12,025.68 BTU/h | 2 × |
| Good | 0.113 | 20,828 BTU/h | 6,329.083 BTU/h | 3.3 × |
| Excellent | 0.093 | 17,142 BTU/h | 5,197.855 BTU/h | 3.3 × |
Heat to deliver by garage size and insulation, 8 ft ceiling, 40°F rise
| Garage | Average (0.133) | Good (0.113) | Excellent (0.093) | 40 BTU/h per sq ft rule |
|---|---|---|---|---|
| 1-car, 12 × 20 ft (240 sq ft) | 10,214 BTU/h | 8,678 BTU/h | 7,142 BTU/h | 9,600 BTU/h |
| 1.5-car, 16 × 24 ft (384 sq ft) | 16,343 BTU/h | 13,885 BTU/h | 11,428 BTU/h | 15,360 BTU/h |
| 2-car, 24 × 24 ft (576 sq ft) | 24,515 BTU/h | 20,828 BTU/h | 17,142 BTU/h | 23,040 BTU/h |
| 3-car, 32 × 24 ft (768 sq ft) | 32,686 BTU/h | 27,771 BTU/h | 22,856 BTU/h | 30,720 BTU/h |
Electric heater size, current at 240 V and breaker
| Heater | Heat output | Current at 240 V | 125% of current | Breaker |
|---|---|---|---|---|
| 3,000 W (3 kW) | 10,236 BTU/h | 12.5 A | 15.6 A | 20 A |
| 4,000 W (4 kW) | 13,649 BTU/h | 16.7 A | 20.8 A | 25 A |
| 5,000 W (5 kW) | 17,061 BTU/h | 20.8 A | 26 A | 30 A |
| 7,500 W (7.5 kW) | 25,591 BTU/h | 31.3 A | 39.1 A | 40 A |
| 10,000 W (10 kW) | 34,121 BTU/h | 41.7 A | 52.1 A | 60 A |
Gas unit heater input sizes and fuel burned at full fire
| Input | Modine’s garage size | Propane | Natural gas |
|---|---|---|---|
| 30,000 BTU/h | 1 to 1.5 car garage | 0.33 gal/h | 29 cu ft/h |
| 45,000 BTU/h | 2 to 2.5 car garage | 0.49 gal/h | 43 cu ft/h |
| 60,000 BTU/h | 3 to 3.5 car garage | 0.66 gal/h | 58 cu ft/h |
| 75,000 BTU/h | large garage or shop | 0.82 gal/h | 72 cu ft/h |
| 100,000 BTU/h | large garage or shop | 1.09 gal/h | 97 cu ft/h |
| 125,000 BTU/h | large garage or shop | 1.37 gal/h | 121 cu ft/h |
Methodology & assumptions
This is an estimate, not a heat-loss calculation. It uses the volume method that garage-heater guides publish: heat to deliver (BTU/h) = garage volume (cu ft) × desired temperature rise (°F) × an insulation factor. 1) Volume = length × width × ceiling height. 2) Temperature rise = the temperature you want inside minus the coldest outdoor temperature you plan to heat through; use a realistic cold-snap temperature for your area, not the all-time record. 3) The factor is in BTU/h per cu ft per °F. The one most guides print is 0.133 for an average garage (Intry). Other guides print lower figures for better-insulated garages: Car Guy Garage uses 0.113 and 0.093, and Combustion Research prints ranges of roughly 0.09 to 0.11 for a well-insulated garage and 0.12 to 0.14 for moderate insulation. This page uses 0.173 for poor, 0.133 for average, 0.113 for good, 0.093 for excellent. The poor-insulation figure is 0.133 × 1.3, following Intry’s advice to add about 30% for an uninsulated garage; that, and the four-way split of the insulation levels, is this site’s interpretation of those guides, so the factors are typical figures, not published tables. Guides disagree, and some use a different scale altogether (an insulation number of 1 to 5 times cu ft times rise, divided by 1.6), so do not mix factors from different formulas. 4) The result is treated as heat delivered to the garage. Gas heaters are sold by INPUT, so the gas input = heat ÷ efficiency: Modine’s Hot Dawg spec sheet lists output at about 82% to 83% of input (30,000 BTU/h input gives about 24,900 output), so 82% is the default, and a vent-free heater is typically listed near 99%. 5) Smallest common size: Modine’s Hot Dawg garage unit heaters come in 30,000, 45,000, 60,000, 75,000, 100,000, 125,000 BTU/h input; the tool shows the smallest one at or above your input, and says so when the input is above 125,000. Other makers sell other sizes. 6) Fuel burn at full fire: propane gal/h = input ÷ 91,452 BTU per gallon and natural gas cu ft/h = input ÷ 1,036 BTU per cu ft, both US Energy Information Administration conversion factors (approximate, and gas heat content varies). A thermostat cycles the heater, so real use is lower; use the propane usage calculator for tank life. 7) Electric: watts = BTU/h ÷ 3.41214, because resistance heat turns all its electricity into heat. Amps at 240 V = watts ÷ 240 (P ÷ V). Fixed electric space heating counts as a continuous load, so the branch circuit and breaker must carry at least 125% of the heater’s current (National Electrical Code Article 210 and 424); the tool shows the next standard breaker size (15, 20, 25, 30, 35, 40, 45, 50, 60 A) and flags anything above 60 A. The breaker, wire gauge and whether your panel can carry the load are for a licensed electrician, and a 120 V plug-in heater is limited to about 1,440 W on a 15 A circuit. A heat pump or ductless mini-split can deliver the same heat for far less electricity but is sized by its rated capacity at your outdoor temperature, which this tool does not do. 8) Cross-check with the room heat loss calculator on this site: that page adds up U-factor × area × temperature difference for each surface and 0.018 × air changes per hour × volume × temperature difference for air leakage. The cross-check line repeats that method for this garage with a typical envelope for each insulation level (wall U-factor from the wall R-value calculator, ceiling U = 1 ÷ (R + 1.67), the room tool’s door U-factors, a slab floor not counted, and 0.5 to 1.5 air changes per hour). It is steady-state heat loss at the temperature rise, so it has no allowance for warming the building up or for the overhead door being opened; for a typical garage it comes out well below the volume method, which is why the volume method is the cautious choice for a heater and the heat-loss method is the better guide to running cost and to how much insulating would shrink the heater. The two measure different things and are not meant to match. Not covered: heating the slab and the cars from cold, a leaky or often-open door, an attached garage with a heated wall (needs less), wind, altitude derating of gas heaters, and venting, combustion air and clearances, which your heater’s manual and local code decide.
- Mr. Heater (Enerco), General Product Info: the maker’s rule of thumb, square footage × 40 = required BTUs, with ceiling height, building layout and insulation level also affecting the need. Used for the square-foot comparison line
- Modine, Homeowners FAQs: lists what sizing depends on (continuous or intermittent use, temperature set point, wall, roof and floor construction, doors and windows, insulation R-value) and pairs Hot Dawg gas input sizes with garage sizes; Modine publishes no volume formula
- Modine, Hot Dawg Gas-Fired Unit Heater (HD/HDS) data sheet: input sizes of 30,000, 45,000, 60,000, 75,000, 100,000 and 125,000 BTU/h, outputs of about 82% to 83% of input, and the garage sizes each suits (30: 1 to 1.5 car, 45: 2 to 2.5 car, 60: 3 to 3.5 car). Read through a distributor listing of the sheet
- Intry, What Size Heater for a Garage? BTU by Car Size: the formula cu ft × 0.133 × temperature rise for an average-insulation garage, and adding about 30% for an uninsulated one
- Car Guy Garage, Garage Heating Guide: How to Determine the Right BTU: lower factors of 0.113 (well insulated) and 0.093 (fully insulated) for the same volume × rise method
- Combustion Research, How to Determine Heater Size in BTU: factor ranges of roughly 0.12 to 0.14 for moderate insulation and 0.09 to 0.11 for well-insulated garages
- US Energy Information Administration, Units and calculators explained: British thermal units (Btu): 1 gallon of propane = 91,452 Btu and 1 cubic foot of natural gas = 1,036 Btu (approximate, updated yearly in the Monthly Energy Review)
- Electrical Construction & Maintenance, Article 424: Fixed Electric Space Heating: fixed electric space heating is treated as a continuous load, so the branch-circuit conductors and overcurrent device are sized at 125% of the heater load (NEC 210.19(A)(1), 210.20(A) and 424.3(B), renumbered 424.4(B) in the 2020 edition)
- NFPA 70, National Electrical Code, Section 240.6(A): the standard ratings of overcurrent devices (15, 20, 25, 30, 35, 40, 45, 50, 60 A and up) used for the breaker line. Cited by name; check the edition your jurisdiction has adopted
- The room heat loss calculator on this site (U × area × ΔT and 0.018 × ACH × volume × ΔT, with the wall R-value calculator’s wall U-factor): the method behind the cross-check line. Its sources are listed on that page
- Typical figures, not published tables: the 0.173 and the four-way insulation levels, the 99% vent-free efficiency, the 9 × 7 ft and 16 × 7 ft door sizes and the air-change rates in the cross-check. Treat every result here as an estimate
How to estimate the heater size for a garage
- Find the garage volume. Multiply the length, width and ceiling height in feet to get cubic feet. A 24 × 24 ft garage with 8 ft ceilings is 4,608 cu ft.
- Choose a temperature rise. Subtract the coldest outdoor temperature you will heat through from the temperature you want inside. To hold 60°F when it is 20°F outside, the rise is 40°F.
- Pick the insulation factor. Use about 0.133 BTU/h per cu ft per °F for average insulation, lower for a well-insulated garage (about 0.093 to 0.113) and higher for an uninsulated one (about 0.173).
- Multiply to get the heat to deliver. BTU/h = cubic feet × temperature rise × factor. For the example, 4,608 × 40 × 0.133 is about 24,500 BTU/h.
- Convert to the heater you will buy. For gas, divide by the heater efficiency (about 0.82 for a vented unit heater) to get the input rating. For electric, divide the BTU/h by 3.41214 for watts and by 240 for amps, then size the breaker at 125% of the amps. Ask an electrician or a heating contractor to confirm.
Worked examples
| Project | Result |
|---|---|
| 24 × 24 ft two-car garage, 8 ft ceiling, average insulation, 40°F rise, 82% gas heater | 24,515 BTU/h to deliver, 29,896 BTU/h gas input (30,000 size), 7.18 kW and 29.9 A at 240 V |
| The same garage with poor insulation (0.173) | 31,887 BTU/h to deliver, 38,887 BTU/h gas input, 38.9 A at 240 V |
| The same garage with good insulation (0.113) | 20,828 BTU/h to deliver, 25,400 BTU/h gas input, 25.4 A at 240 V |
| One-car 12 × 20 ft garage, good insulation, single door | 8,678 BTU/h to deliver, 10,583 BTU/h gas input (30,000 size), 2.54 kW and 10.6 A at 240 V |
| The default garage with a 10 ft ceiling (volume × 1.25) | 30,643 BTU/h to deliver, 37,370 BTU/h gas input |
| The default garage held 60°F above outdoors (0°F outside, 60°F inside) | 36,772 BTU/h to deliver, 44,844 BTU/h gas input, 44.9 A at 240 V |
| The default garage with a 99% vent-free gas heater | 24,515 BTU/h to deliver, only 24,763 BTU/h of gas input |
| 30 × 40 ft shop, 10 ft ceiling, average insulation, 50°F rise | 79,800 BTU/h to deliver, 97,317 BTU/h gas input (100,000 size), 23.39 kW |
Frequently asked questions
- How many BTU do I need to heat my garage?
- Multiply the garage volume in cubic feet by the temperature rise you want in °F and by an insulation factor, 0.133 for an average garage. A 24 × 24 ft garage with 8 ft ceilings is 4,608 cu ft, so a 40°F rise needs 24,515 BTU/h of heat; with good insulation (0.113) it is 20,828 BTU/h and with poor insulation (0.173) 31,887 BTU/h. Because gas heaters are sold by input, divide by the heater’s efficiency: 29,896 BTU/h input at 82%. This is an estimate; a heat-loss calculation is more exact.
- What is the formula for sizing a garage heater?
- BTU/h = length × width × ceiling height × temperature rise (°F) × factor. The factor most garage guides print is 0.133 for average insulation, with lower values (about 0.09 to 0.11) for well-insulated garages and a higher one (about 30% more) for an uninsulated one. Some guides use a different scale, such as an insulation number times cubic feet times rise divided by 1.6; the two scales are not interchangeable, so use one formula with its own factors.
- What temperature rise should I use?
- The rise is the temperature you want inside minus the coldest outdoor temperature you intend to keep heating through. To hold 60°F when it is 20°F outside, use 40°F; to hold 55°F at 0°F, use 55°F. Use a cold-snap temperature that happens most winters rather than the record low, and remember that a bigger rise needs a bigger heater: going from 40°F to 60°F takes the default garage from 24,515 BTU/h to 36,772 BTU/h.
- How big a propane or natural gas heater do I need?
- Take the heat to deliver and divide by the heater’s efficiency to get the input in BTU/h, since gas heaters are rated by input. The default garage needs 24,515 BTU/h delivered, which is 29,896 BTU/h input at 82%, so a 30,000 BTU/h unit covers it. A propane or natural gas version of the same size has the same BTU/h rating (natural gas units use a different orifice, and a conversion kit is needed to switch). At full fire it burns 0.33 gal/h of propane or 29 cu ft/h of natural gas. Modine pairs its 30,000 BTU/h Hot Dawg with a 1 to 1.5 car garage and its 45,000 with a 2 to 2.5 car garage, which is a little more heater than this estimate gives for a typical rise; extra capacity is what recovers the temperature after the door has been open.
- How many kW and how many amps does an electric garage heater need?
- Convert BTU/h to watts by dividing by 3.41214, then amps = watts ÷ volts. The default garage needs 24,515 BTU/h, which is 7,185 W or 7.18 kW, so 29.9 A at 240 V (watts ÷ 240). A heater that is a continuous load needs a circuit that carries 125% of that, 37.4 A, so a 40 A breaker. Heaters come in steps (for example 5,000, 7,500 and 10,000 W), so pick the next size up, and have an electrician check the wire gauge and the panel. A 120 V heater on a 15 A circuit tops out at about 1,440 W continuous, far too little for most garages.
- Is an electric or a gas garage heater cheaper to run?
- Gas is usually cheaper per BTU, and electric resistance is the simplest to install. Resistance heat gives 3,412 BTU per kWh, so the default garage at full output uses about 7.18 kW per hour; at 15 cents per kWh that is about $1.08 an hour, while the gas version burns 0.33 gal/h of propane, so multiply by your price per gallon to compare. Compare the two with your own rates; the electricity cost calculator and the propane usage calculator on this site do the arithmetic. A heat pump or mini-split can beat both when it is rated for your outdoor temperature.
- How much does insulation change the heater size?
- A lot. For the 24 × 24 ft garage with a 40°F rise, this calculator gives 31,887 BTU/h for poor insulation, 24,515 BTU/h for average, 20,828 BTU/h for good and 17,142 BTU/h for excellent. Insulating the walls and ceiling, fitting an insulated garage door and sealing the door edges often costs less than the extra heater capacity and then cuts the running cost every winter.
- How does a taller ceiling change the size?
- The volume method scales with ceiling height, so a 10 ft ceiling needs 25% more heat than an 8 ft ceiling: the default 24 × 24 ft garage goes from 24,515 BTU/h to 30,643 BTU/h. Warm air collects near the ceiling, so in a tall garage a ceiling fan or a radiant heater that warms people and objects directly helps; a recirculating fan is cheap compared with a bigger heater.
- Is this the same as a heat loss calculation?
- No. The volume method is a quick rule that folds the walls, ceiling, door and air leakage into one factor. A heat-loss calculation, like the room heat loss calculator on this site, adds up each surface’s U-factor × area × temperature difference plus air leakage. For the default garage that method gives about 12,026 BTU/h against 24,515 BTU/h here, so the volume method is deliberately cautious: it leaves room for the door being opened and for warming the building and what is in it. Use the heat-loss method to see what insulating would save, and the volume method to choose the heater.
- Can I use a vent-free or unvented heater in a garage?
- Many codes and manufacturers restrict vent-free gas heaters in garages and require ignition sources to be kept off the floor, away from gasoline fumes, with working carbon monoxide detection and adequate combustion air. Read the heater’s manual and ask your building department before installing any gas heater in a garage; the unvented type also puts moisture and combustion gases into the space, which is why this tool shows the vented 82% efficiency as the default.
- Does an attached garage need a smaller heater?
- Usually yes. A wall shared with the heated house loses little heat, so an attached garage needs less than a detached one of the same size. This estimate does not model that, so treat the result as an upper figure, or choose the next better insulation level. A garage with a ceiling under living space also loses less through the ceiling.
- How does this compare with the "40 BTU per square foot" rule?
- Mr. Heater suggests about 40 BTU/h per sq ft, which is 23,040 BTU/h for a 576 sq ft garage, close to the 24,515 BTU/h here. A square-foot rule cannot see the ceiling height or the temperature rise: this calculator moves to 30,643 BTU/h for a 10 ft ceiling and 79,800 BTU/h for a 30 × 40 ft shop with a 10 ft ceiling and a 50°F rise, where the rule would say 48,000 BTU/h.
Handy tools
- Wire Size Calculator: Pick the wire gauge for the 240 V circuit once you know the amps and the run length.
- Electricity Cost Calculator: Turn the heater’s kW and your hours of use into a running cost per month.
- Generator Size Calculator: Check what generator it takes to run an electric garage heater in an outage.