Electric Radiant Floor Heating Calculator: Watts, Amps and Running Cost

A 10 × 8 ft bathroom (80 sq ft) with about 80% of the floor clear of the vanity, toilet and tub has 64 sq ft to heat. A typical 120 V mat at 12 W/sq ft then draws 768 W (0.77 kW), which is 6.4 A at 120 V or 3.2 A at 240 V. One 15 A thermostat covers it, and because floor heat counts as a continuous load the breaker must carry 125% of the current, so a 15 A breaker. At 6 hours of full power a day and 18 cents per kWh it costs about $0.83 a day, or $24.88 a month. Enter your own room, the share you will heat, the product’s watts per square foot, the voltage and your rate. These are planning estimates: use the maker’s load table and have an electrician size the circuit.

Figures based on the sources listed belowUpdated How we calculate

Mats go only where you will stand or walk: not under cabinets, a tub, a toilet base or any fixture. Typically 70% to 90% of the room. If you list every fixture under "area to leave out", pick 100%.

The watts per square foot printed on the mat or the cable spacing chart. SunTouch and Nuheat mats are 12 W/sq ft; Schluter DITRA-HEAT cable is about 12.7 W/sq ft at its standard spacing and about 15 W/sq ft when laid closer. Use your product’s figure.
The voltage of the mat you buy: a 120 V mat cannot run on 240 V or the reverse. The same floor draws half the amps at 240 V, so one thermostat carries twice the area.

Hours at full power, not hours the thermostat is set on: it cycles the heat on and off, so a floor “on” for 12 hours may draw full power for 4 to 6. An estimate.

Your price per kWh from your bill. The US residential average has run about 18 cents in recent years (EIA).

64 sq ft to heat.

64 sq ft to heat

  • Total power: 768 W (0.77 kW): 64 sq ft × 12 W/sq ft
  • Current at 120 V: 6.4 A (768 W ÷ 120 V)
  • Current at 240 V: 3.2 A (768 W ÷ 240 V), half the 120 V current
  • Thermostats and circuits (120 V, 15 A each): 1 thermostat on 1 circuit: 6.4 A is within its 15 A limit
  • Breaker per circuit (125% of the load): 15 A breaker (6.4 A × 1.25 = 8 A, next standard size), single-pole; an electrician sets the wire and breaker
  • Most one thermostat carries (120 V): 150 sq ft of heated floor at 12 W/sq ft (15 A × 120 V ÷ 12); the same floor at 240 V is 300 sq ft
  • Heat output: 2,621 BTU/h (0.77 kW × 3,412 BTU/h per kW); floor heat is usually comfort heat on top of the room's main heating
  • Energy per day: 4.61 kWh (0.77 kW × 6 h at full power)
  • Running cost per day: $0.83 per day at $0.18 per kWh
  • Running cost per month (30 days): $24.88 per month (138.2 kWh); a thermostat cycles the heat, so the real figure is lower

Shopping list

  • Electric floor heating mat, 120 V
  • Programmable floor heat thermostat with GFCI
  • Floor heating cable installation tape
  • Multimeter (check resistance before and after tiling)
  • Tape measure (25 ft)
Show diagram

Saved projects

No saved projects yet.

Watts, amps, thermostats and breaker by heated area at 12 W/sq ft

Heated area is the mat or cable area, not the room. Amps at both voltages; thermostats and breaker are for a 120 V supply (a 15 A thermostat each, breaker at 125% of the current per circuit).
Heated areaTotal powerCurrent at 120 VCurrent at 240 VThermostatsBreaker per circuit
25 sq ft300 W2.5 A1.3 A1 (at 120 V)15 A
50 sq ft600 W5 A2.5 A1 (at 120 V)15 A
75 sq ft900 W7.5 A3.8 A1 (at 120 V)15 A
100 sq ft1,200 W10 A5 A1 (at 120 V)15 A
150 sq ft1,800 W15 A7.5 A1 (at 120 V)20 A
200 sq ft2,400 W20 A10 A2 (at 120 V)15 A
300 sq ft3,600 W30 A15 A2 (at 120 V)20 A

Most floor one 15 A thermostat carries

15 A × volts ÷ watts per sq ft. 12 W/sq ft is the SunTouch and Nuheat mat rating, 12.7 the Schluter DITRA-HEAT cable at standard spacing and 15 a close-spaced high-output figure (an estimate). SunTouch states 150 sq ft at 120 V and 300 sq ft at 240 V for its 12 W/sq ft mats.
OutputAt 120 VAt 240 V
12 W/sq ft150 sq ft300 sq ft
12.7 W/sq ft142 sq ft283 sq ft
15 W/sq ft120 sq ft240 sq ft

Running cost by heated area, 6 hours at full power a day, 30-day month

At 12 W/sq ft and 18 cents per kWh. Cost scales directly with watts per sq ft, hours and rate; a thermostat that cycles the mat uses less than these full-power figures.
Heated areaEnergy per dayCost per dayCost per month
25 sq ft1.8 kWh$0.32$9.72
50 sq ft3.6 kWh$0.65$19.44
100 sq ft7.2 kWh$1.30$38.88
200 sq ft14.4 kWh$2.59$77.76

Typical heated share of the floor, by room

Typical figures (estimates) for how much of the floor is left after cabinets and fixtures. Measure your own room: mats go only where the floor is clear.
RoomShare of the floor to heat
Small bathroom (vanity, toilet, tub)60% to 75%
Master bathroom with a walk-in shower70% to 85%
Entry, mudroom or hallway85% to 100%
Kitchen with a perimeter of cabinets50% to 70%
Open room with only furniture90% to 100%

Methodology & assumptions

This is a planning estimate for electric resistance floor heating (mats and cables under tile, in thinset or self-leveling compound). 1) Heated area = room length × width × the share of the floor you will heat, less any areas you add to leave out. Mats and cables go only where you stand or walk, so cabinets, a tub, a toilet base and a shower pan are left out; heated area is typically 70% to 90% of a bathroom floor (a typical figure, not a published rule), less in a kitchen with cabinets. Pick 100% if you list every fixture as an area to leave out, so nothing is taken off twice. Heated area is the number of square feet of mat or cable you order; mats cannot be cut, so the real order is the nearest size the maker sells. 2) Total watts = heated area × watts per square foot. SunTouch TapeMat and Nuheat mats are rated 12 W/sq ft at 120 V (a 24 in × 40 in TapeMat is 120 W per 10 sq ft). Schluter DITRA-HEAT cable is about 12.7 W/sq ft at its standard 3-stud spacing and about 15.2 W/sq ft in a closer 3-2-3-2 pattern, as retailers list it; Warmup prints 13.1 W/sq ft for its cable at both 120 V and 240 V. So 12 W/sq ft is the default and 15 W/sq ft the typical high-output figure (an estimate); use the watts per square foot on your product. 3) Amps = watts ÷ volts, shown at both 120 V and 240 V. The same mat output draws half the current at 240 V. 4) Thermostats: floor-heating thermostats switch a limited load. SunTouch’s SunStat limit is 15 A, which it states as 150 sq ft of 120 V mat or 300 sq ft of 240 V mat (12 W/sq ft), and Nuheat’s and Schluter’s DITRA-HEAT-E-R are also 15 A. So thermostats = amps ÷ 15, rounded up. Over the limit, the heated area is split between thermostats, each on its own circuit, and the amps are shared evenly; Schluter also sells a power module for loads over 15 A that keeps one control point. 5) Breaker: fixed electric space heating is a continuous load, so the branch circuit and breaker must carry at least 125% of the load (National Electrical Code Article 210 and 424; the same rule the garage heater size page uses). The tool shows the next standard size (15 or 20 A): a load up to 12 A gets a 15 A breaker and 12.1 A to 15 A gets a 20 A breaker, the pairing in SunTouch’s wiring table (14 AWG up to 12 A, 12 AWG up to 15 A on a 20 A breaker). Most manuals also want a dedicated circuit and a GFCI, which the thermostats usually include (a Class A GFCI is built into the SunStat and Schluter’s thermostat). Wire gauge, breaker, GFCI and permits are for a licensed electrician and your local code; a 120 V circuit uses a single-pole breaker and a 240 V circuit a double-pole one. 6) Heat output = kW × 3,412 BTU/h. Compare it with the room’s heat loss on the room heat loss page: 12 W/sq ft over an 80% floor is a comfort layer, enough to warm the floor, and it is usually not the room’s only heat. 7) Running cost = kW × hours at full power per day × rate per kWh, and monthly cost counts 30 days. The hours are hours of full power, not hours the thermostat is on: it cycles the mat, so the real figure is lower. The default rate of 18 cents per kWh follows the electricity cost calculator’s US residential average from the US Energy Information Administration; use the rate on your bill. Not covered: insulation boards under the mat (which cut the energy used to warm the slab), warm-up time, the floor sensor’s set point, a mat spacing chart for loose cable, and any local rule about shower floors, which usually needs the inspector’s approval.

How to size an electric radiant floor heating system

  1. Find the heated area. Multiply the room length by the width and take out cabinets, a tub, a toilet base and other fixtures. In a bathroom the heated area is typically 70% to 90% of the floor. For a 10 × 8 ft bathroom at 80% it is 64 sq ft.
  2. Choose the watts per square foot. Use the rating on the mat or the cable spacing chart. SunTouch and Nuheat mats are 12 W/sq ft; cable systems run about 12.7 to 15 W/sq ft depending on spacing.
  3. Multiply to get the total watts. Watts = heated area × watts per square foot. For the example, 64 sq ft × 12 W/sq ft = 768 W.
  4. Convert to amps at your voltage. Amps = watts ÷ volts: 768 W is 6.4 A at 120 V and 3.2 A at 240 V. Buy a mat made for the voltage you will wire.
  5. Count the thermostats and size the breaker. One 15 A thermostat per 15 A of load, each on its own circuit. Multiply each circuit’s amps by 1.25 (a continuous load) and round up to the next standard breaker, 15 A up to 12 A of load and 20 A above that. An electrician confirms the wire and the GFCI.
  6. Work out the running cost. kWh per day = kW × hours at full power; multiply by your rate per kWh and by 30 for a month. The thermostat cycles the mat, so the real cost is lower.

Worked examples

ProjectResult
10 × 8 ft bathroom, 80% heated, 12 W/sq ft mat on 120 V, 6 h a day at 18 cents64 sq ft to heat: 768 W, 6.4 A at 120 V, 1 thermostat, 15 A breaker, $24.88 a month
The same bathroom with every square foot heated (100%)80 sq ft to heat: 960 W, 8 A at 120 V, $31.10 a month
The same bathroom with a 5 × 2.5 ft vanity and a 3 × 2 ft toilet area entered as areas to leave out (100% share)61.5 sq ft to heat: 738 W, 6.2 A at 120 V, 15 A breaker
The default bathroom with a 15 W/sq ft mat64 sq ft to heat: 960 W, 8 A at 120 V, 15 A breaker
The default bathroom on 240 V64 sq ft to heat: 768 W, 3.2 A at 240 V, 15 A breaker
12 × 14 ft kitchen, 60% heated between the cabinets100.8 sq ft to heat: 1,210 W, 10.1 A at 120 V, 1 thermostat, 15 A breaker
20 × 20 ft open room, 90% heated, 12 W/sq ft on 120 V360 sq ft to heat: 4,320 W, 36 A at 120 V, 3 thermostats on 3 circuits of 12 A, 15 A breaker each
The default bathroom run 12 hours a day at 30 cents per kWh64 sq ft to heat: 768 W, $2.76 a day, $82.94 a month

Frequently asked questions

How many watts per square foot do I need for floor heating?
Most electric mats are 12 W/sq ft: that is the rating of SunTouch TapeMat and Nuheat mats. Cable systems vary with spacing, for example Schluter DITRA-HEAT is about 12.7 W/sq ft at standard spacing and about 15 W/sq ft laid closer, and Warmup prints 13.1. Twelve watts per square foot is enough for comfort heat under tile; 15 gives about 25% more heat, which suits a floor that must carry more of the room’s heat. For the default room, 64 sq ft at 12 W/sq ft is 768 W, and at 15 W/sq ft 960 W.
How much of the floor should I heat?
Only the floor you stand on. Leave out cabinets, a tub, a toilet base, a shower pan and anything built in; in a bathroom that is typically 70% to 90% of the floor, less in a kitchen. The 10 × 8 ft bathroom (80 sq ft) is 64 sq ft to heat at 80%; heating all 80 sq ft would be 80 sq ft to heat and 960 W, and 192 W more for floor nobody walks on. You can also enter each fixture as an area to leave out and choose 100%.
How many amps does a heated floor draw?
Amps = watts ÷ volts. The default bathroom is 768 W, so 6.4 A at 120 V and 3.2 A at 240 V. A bigger floor adds up fast: a 20 × 20 ft room heated at 90% is 360 sq ft to heat, which is 4,320 W and 36 A at 120 V (more than one 15 A thermostat) or 18 A at 240 V.
What size breaker does a heated floor need?
Fixed electric space heating is a continuous load, so the circuit and breaker must carry 125% of the current (NEC Article 424, the same rule as for an electric garage heater). The default floor draws 6.4 A, times 1.25 is 8 A, so a 15 A breaker. A full 15 A thermostat load needs a 20 A breaker (15 × 1.25 = 18.75). SunTouch’s wiring table pairs up to 12 A with 14 AWG wire on a 15 or 20 A breaker and up to 15 A with 12 AWG on a 20 A breaker. Floor heat usually needs its own circuit and a GFCI; ask an electrician.
How many thermostats do I need?
One per 15 A of load, each on its own circuit. SunTouch’s SunStat and Schluter’s DITRA-HEAT-E-R are 15 A, which SunTouch states as 150 sq ft of 12 W/sq ft mat at 120 V or 300 sq ft at 240 V. A 20 × 20 ft room heated at 90% (360 sq ft, 36 A at 120 V) needs 3 thermostats at 120 V, or 2 at 240 V even with a 15 W/sq ft mat (22.5 A). Schluter sells a power module so one control point can run loads over 15 A.
Should I use 120 V or 240 V?
Both give the same heat for the same watts per square foot. The difference is current: 240 V draws half the amps, so one thermostat carries twice the floor (300 sq ft instead of 150 at 12 W/sq ft) and the wire can be smaller. The default floor is 6.4 A at 120 V and 3.2 A at 240 V. A 120 V mat is simpler for a small bathroom, since a 15 A or 20 A 120 V circuit is usually there; choose 240 V for a large floor, and buy the mat in the voltage you will wire, as the two cannot be swapped.
How much does it cost to run a heated floor?
Cost = kW × hours at full power × rate. The default floor is 0.77 kW, so 6 hours at 18 cents per kWh is $0.83 a day and $24.88 over 30 days. Run it 12 hours at 30 cents and it is $2.76 a day, $82.94 a month. The thermostat cycles the mat, so a floor set on for many hours uses full power for only part of them, and a programmable thermostat that warms the floor before you wake cuts the hours. The electricity cost calculator on this site does the same sum for any appliance.
Is radiant floor heat enough to heat a room?
Usually not on its own. The default floor puts out about 2,621 BTU/h, comfort heat that takes the chill off tile. Whether it can heat a room depends on the room’s heat loss: use the room heat loss calculator on this site to see the BTU/h at your design temperature, and compare it with the floor’s output. In a well-insulated bathroom it can carry the load; in a cold, leaky room it is a supplement.
Does the area under cabinets or the tub need heat?
No. Heat under cabinets and a tub has nowhere to go and can overheat the flooring; most makers say to keep mats and cable out from under fixed fixtures and at least a few inches from walls, toilets and drains. Check your product’s manual for the exact clearance. The calculator takes these out through the share of the floor to heat or the areas you leave out.
Can I cut a heating mat to fit?
No. The heating element is a fixed length, and cutting it changes the resistance or breaks the circuit. Nuheat mats and Schluter cables are not cut. You cut the mesh or the backing between the runs and turn the mat around to fit a layout, and the cable is laid at a spacing that fits the area. Because of that, you order the nearest available mat size (the order is usually a little more or less than the heated area), and the watts in the maker’s catalog, not this estimate, set the real load.
What goes under and over the heating mat?
Mats and cables are set in thinset on a clean, flat subfloor, or on cement board, and then covered with tile and its mortar or with self-leveling compound. A flat floor matters: use the self-leveling underlayment calculator if the subfloor is out of level, and the cement board calculator for the backer. An insulation board under the mat can shorten warm-up time and cut running cost. Always check the heating resistance with a meter before, during and after the tile goes down.
How does a 15 W/sq ft mat change the numbers?
Everything scales by 15 ÷ 12, so the default bathroom goes from 768 W to 960 W and from 6.4 A to 8 A at 120 V, and the monthly cost from $24.88 to $31.10. One thermostat then covers 120 sq ft at 120 V rather than 150. A 15 W/sq ft output is a typical high-output figure, so check what your product actually offers.