Electric Radiant Floor Heating Calculator: Watts, Amps and Running Cost
A 10 × 8 ft bathroom (80 sq ft) with about 80% of the floor clear of the vanity, toilet and tub has 64 sq ft to heat. A typical 120 V mat at 12 W/sq ft then draws 768 W (0.77 kW), which is 6.4 A at 120 V or 3.2 A at 240 V. One 15 A thermostat covers it, and because floor heat counts as a continuous load the breaker must carry 125% of the current, so a 15 A breaker. At 6 hours of full power a day and 18 cents per kWh it costs about $0.83 a day, or $24.88 a month. Enter your own room, the share you will heat, the product’s watts per square foot, the voltage and your rate. These are planning estimates: use the maker’s load table and have an electrician size the circuit.
Figures based on the sources listed belowUpdated How we calculate
64 sq ft to heat.
64 sq ft to heat
- Total power: 768 W (0.77 kW): 64 sq ft × 12 W/sq ft
- Current at 120 V: 6.4 A (768 W ÷ 120 V)
- Current at 240 V: 3.2 A (768 W ÷ 240 V), half the 120 V current
- Thermostats and circuits (120 V, 15 A each): 1 thermostat on 1 circuit: 6.4 A is within its 15 A limit
- Breaker per circuit (125% of the load): 15 A breaker (6.4 A × 1.25 = 8 A, next standard size), single-pole; an electrician sets the wire and breaker
- Most one thermostat carries (120 V): 150 sq ft of heated floor at 12 W/sq ft (15 A × 120 V ÷ 12); the same floor at 240 V is 300 sq ft
- Heat output: 2,621 BTU/h (0.77 kW × 3,412 BTU/h per kW); floor heat is usually comfort heat on top of the room's main heating
- Energy per day: 4.61 kWh (0.77 kW × 6 h at full power)
- Running cost per day: $0.83 per day at $0.18 per kWh
- Running cost per month (30 days): $24.88 per month (138.2 kWh); a thermostat cycles the heat, so the real figure is lower
Shopping list
- Electric floor heating mat, 120 V
- Programmable floor heat thermostat with GFCI
- Floor heating cable installation tape
- Multimeter (check resistance before and after tiling)
- Tape measure (25 ft)
Your project
- Room length × room width: 10 × 8 ft
- Share of the floor to heat: 80%: typical bathroom with a vanity
- Mat or cable output: 12 W/sq ft
- Supply voltage: 120 V
- Hours on per day: 6 h
- Electricity rate: 0.18 $/kWh
Also pick up
- Electric floor heating mat, 120 V
- Programmable floor heat thermostat with GFCI
- Floor heating cable installation tape
- Multimeter (check resistance before and after tiling)
- Tape measure (25 ft)
Reopen this calculation: /calculators/radiant-floor-heating/?s=eyJyb29tIjp7Imxlbmd0aEZ0IjoxMCwid2lkdGhGdCI6OH0sImRlZHVjdGlvbnMiOltdLCJ3YXN0ZVBjdCI6MC4xLCJwYXJhbXMiOnsiaGVhdGVkUGN0Ijo4MCwid2F0dHNQZXJTcUZ0IjoxMiwidm9sdHMiOjEyMCwiaG91cnNQZXJEYXkiOjYsInJhdGVQZXJLd2giOjAuMTh9fQ
Show diagram
Saved projects
No saved projects yet.
Watts, amps, thermostats and breaker by heated area at 12 W/sq ft
| Heated area | Total power | Current at 120 V | Current at 240 V | Thermostats | Breaker per circuit |
|---|---|---|---|---|---|
| 25 sq ft | 300 W | 2.5 A | 1.3 A | 1 (at 120 V) | 15 A |
| 50 sq ft | 600 W | 5 A | 2.5 A | 1 (at 120 V) | 15 A |
| 75 sq ft | 900 W | 7.5 A | 3.8 A | 1 (at 120 V) | 15 A |
| 100 sq ft | 1,200 W | 10 A | 5 A | 1 (at 120 V) | 15 A |
| 150 sq ft | 1,800 W | 15 A | 7.5 A | 1 (at 120 V) | 20 A |
| 200 sq ft | 2,400 W | 20 A | 10 A | 2 (at 120 V) | 15 A |
| 300 sq ft | 3,600 W | 30 A | 15 A | 2 (at 120 V) | 20 A |
Most floor one 15 A thermostat carries
| Output | At 120 V | At 240 V |
|---|---|---|
| 12 W/sq ft | 150 sq ft | 300 sq ft |
| 12.7 W/sq ft | 142 sq ft | 283 sq ft |
| 15 W/sq ft | 120 sq ft | 240 sq ft |
Running cost by heated area, 6 hours at full power a day, 30-day month
| Heated area | Energy per day | Cost per day | Cost per month |
|---|---|---|---|
| 25 sq ft | 1.8 kWh | $0.32 | $9.72 |
| 50 sq ft | 3.6 kWh | $0.65 | $19.44 |
| 100 sq ft | 7.2 kWh | $1.30 | $38.88 |
| 200 sq ft | 14.4 kWh | $2.59 | $77.76 |
Typical heated share of the floor, by room
| Room | Share of the floor to heat |
|---|---|
| Small bathroom (vanity, toilet, tub) | 60% to 75% |
| Master bathroom with a walk-in shower | 70% to 85% |
| Entry, mudroom or hallway | 85% to 100% |
| Kitchen with a perimeter of cabinets | 50% to 70% |
| Open room with only furniture | 90% to 100% |
Methodology & assumptions
This is a planning estimate for electric resistance floor heating (mats and cables under tile, in thinset or self-leveling compound). 1) Heated area = room length × width × the share of the floor you will heat, less any areas you add to leave out. Mats and cables go only where you stand or walk, so cabinets, a tub, a toilet base and a shower pan are left out; heated area is typically 70% to 90% of a bathroom floor (a typical figure, not a published rule), less in a kitchen with cabinets. Pick 100% if you list every fixture as an area to leave out, so nothing is taken off twice. Heated area is the number of square feet of mat or cable you order; mats cannot be cut, so the real order is the nearest size the maker sells. 2) Total watts = heated area × watts per square foot. SunTouch TapeMat and Nuheat mats are rated 12 W/sq ft at 120 V (a 24 in × 40 in TapeMat is 120 W per 10 sq ft). Schluter DITRA-HEAT cable is about 12.7 W/sq ft at its standard 3-stud spacing and about 15.2 W/sq ft in a closer 3-2-3-2 pattern, as retailers list it; Warmup prints 13.1 W/sq ft for its cable at both 120 V and 240 V. So 12 W/sq ft is the default and 15 W/sq ft the typical high-output figure (an estimate); use the watts per square foot on your product. 3) Amps = watts ÷ volts, shown at both 120 V and 240 V. The same mat output draws half the current at 240 V. 4) Thermostats: floor-heating thermostats switch a limited load. SunTouch’s SunStat limit is 15 A, which it states as 150 sq ft of 120 V mat or 300 sq ft of 240 V mat (12 W/sq ft), and Nuheat’s and Schluter’s DITRA-HEAT-E-R are also 15 A. So thermostats = amps ÷ 15, rounded up. Over the limit, the heated area is split between thermostats, each on its own circuit, and the amps are shared evenly; Schluter also sells a power module for loads over 15 A that keeps one control point. 5) Breaker: fixed electric space heating is a continuous load, so the branch circuit and breaker must carry at least 125% of the load (National Electrical Code Article 210 and 424; the same rule the garage heater size page uses). The tool shows the next standard size (15 or 20 A): a load up to 12 A gets a 15 A breaker and 12.1 A to 15 A gets a 20 A breaker, the pairing in SunTouch’s wiring table (14 AWG up to 12 A, 12 AWG up to 15 A on a 20 A breaker). Most manuals also want a dedicated circuit and a GFCI, which the thermostats usually include (a Class A GFCI is built into the SunStat and Schluter’s thermostat). Wire gauge, breaker, GFCI and permits are for a licensed electrician and your local code; a 120 V circuit uses a single-pole breaker and a 240 V circuit a double-pole one. 6) Heat output = kW × 3,412 BTU/h. Compare it with the room’s heat loss on the room heat loss page: 12 W/sq ft over an 80% floor is a comfort layer, enough to warm the floor, and it is usually not the room’s only heat. 7) Running cost = kW × hours at full power per day × rate per kWh, and monthly cost counts 30 days. The hours are hours of full power, not hours the thermostat is on: it cycles the mat, so the real figure is lower. The default rate of 18 cents per kWh follows the electricity cost calculator’s US residential average from the US Energy Information Administration; use the rate on your bill. Not covered: insulation boards under the mat (which cut the energy used to warm the slab), warm-up time, the floor sensor’s set point, a mat spacing chart for loose cable, and any local rule about shower floors, which usually needs the inspector’s approval.
- Warm Your Floor, SunTouch TapeMat 120V 24 in × 10 ft listing: 12 watts per square foot and 120 W per 10 sq ft mat, for installation in mortar or self-leveling compound under tile
- Warm Your Floor, SunTouch SunStat Non-Programmable Dial Control: 15 A relay and built-in GFCI, controlling up to 150 sq ft of 120 V or 300 sq ft of 240 V SunTouch mats (the maker states the maximum load of all SunStats as 15 A)
- SunTouch Floor Warming installation manual (500850-SC), junction boxes and wiring table: up to 12 A on 14 AWG with a 15 or 20 A breaker, up to 15 A on 12 AWG with a 20 A breaker, and a second circuit and control above 15 A. Read through a manual archive; wire sizes are the maker’s recommendation, so follow local code
- Warm Your Floor, Nuheat Mat 84 in × 24 in (120V) listing: up to 12 watts per square foot, 168 W and 1.4 A for the 14 sq ft mat, and several mats on one thermostat up to its 15 A limit
- Schluter-Systems, DITRA-HEAT-E-R thermostat: two heating cables up to a total load of 15 A, 120 V or 240 V, a built-in Class A GFCI, and the DITRA-HEAT-E-RR power module for loads over 15 A
- Warm Your Floor, Schluter DITRA-HEAT Cable listings: about 12.7 W/sq ft at 3-stud spacing and 15.2 W/sq ft at a closer 3-2-3-2 pattern. The cable, not a mat, so output depends on spacing. A retailer’s listing of the maker’s figures
- Warmup, 120V or 240V?: both voltages of its cable put out the same watts per square foot (13.1 W/sq ft), so the voltage changes the current and how much floor one thermostat carries, not the heat
- Electrical Construction & Maintenance, Article 424: Fixed Electric Space Heating: fixed electric space heating is treated as a continuous load, so the branch-circuit conductors and overcurrent device are sized at 125% of the heater load (NEC 210.19(A)(1), 210.20(A) and 424.3(B), renumbered 424.4(B) in the 2020 edition)
- NFPA 70, National Electrical Code, Section 240.6(A): the standard ratings of overcurrent devices (15, 20, 25, 30 A and up) used for the breaker line. Cited by name; check the edition your jurisdiction has adopted
- The electricity cost calculator on this site (watts × hours ÷ 1,000 = kWh) and its US residential average rate from the US Energy Information Administration, Electric Power Monthly, Table 5.6.A, about 18 cents per kWh. Its sources are listed on that page
- Typical figures, not published tables: the 70% to 90% heated share of a room and the per-room shares in the table, the 6 hours at full power a day, and 30 days a month. Treat every result here as an estimate
How to size an electric radiant floor heating system
- Find the heated area. Multiply the room length by the width and take out cabinets, a tub, a toilet base and other fixtures. In a bathroom the heated area is typically 70% to 90% of the floor. For a 10 × 8 ft bathroom at 80% it is 64 sq ft.
- Choose the watts per square foot. Use the rating on the mat or the cable spacing chart. SunTouch and Nuheat mats are 12 W/sq ft; cable systems run about 12.7 to 15 W/sq ft depending on spacing.
- Multiply to get the total watts. Watts = heated area × watts per square foot. For the example, 64 sq ft × 12 W/sq ft = 768 W.
- Convert to amps at your voltage. Amps = watts ÷ volts: 768 W is 6.4 A at 120 V and 3.2 A at 240 V. Buy a mat made for the voltage you will wire.
- Count the thermostats and size the breaker. One 15 A thermostat per 15 A of load, each on its own circuit. Multiply each circuit’s amps by 1.25 (a continuous load) and round up to the next standard breaker, 15 A up to 12 A of load and 20 A above that. An electrician confirms the wire and the GFCI.
- Work out the running cost. kWh per day = kW × hours at full power; multiply by your rate per kWh and by 30 for a month. The thermostat cycles the mat, so the real cost is lower.
Worked examples
| Project | Result |
|---|---|
| 10 × 8 ft bathroom, 80% heated, 12 W/sq ft mat on 120 V, 6 h a day at 18 cents | 64 sq ft to heat: 768 W, 6.4 A at 120 V, 1 thermostat, 15 A breaker, $24.88 a month |
| The same bathroom with every square foot heated (100%) | 80 sq ft to heat: 960 W, 8 A at 120 V, $31.10 a month |
| The same bathroom with a 5 × 2.5 ft vanity and a 3 × 2 ft toilet area entered as areas to leave out (100% share) | 61.5 sq ft to heat: 738 W, 6.2 A at 120 V, 15 A breaker |
| The default bathroom with a 15 W/sq ft mat | 64 sq ft to heat: 960 W, 8 A at 120 V, 15 A breaker |
| The default bathroom on 240 V | 64 sq ft to heat: 768 W, 3.2 A at 240 V, 15 A breaker |
| 12 × 14 ft kitchen, 60% heated between the cabinets | 100.8 sq ft to heat: 1,210 W, 10.1 A at 120 V, 1 thermostat, 15 A breaker |
| 20 × 20 ft open room, 90% heated, 12 W/sq ft on 120 V | 360 sq ft to heat: 4,320 W, 36 A at 120 V, 3 thermostats on 3 circuits of 12 A, 15 A breaker each |
| The default bathroom run 12 hours a day at 30 cents per kWh | 64 sq ft to heat: 768 W, $2.76 a day, $82.94 a month |
Frequently asked questions
- How many watts per square foot do I need for floor heating?
- Most electric mats are 12 W/sq ft: that is the rating of SunTouch TapeMat and Nuheat mats. Cable systems vary with spacing, for example Schluter DITRA-HEAT is about 12.7 W/sq ft at standard spacing and about 15 W/sq ft laid closer, and Warmup prints 13.1. Twelve watts per square foot is enough for comfort heat under tile; 15 gives about 25% more heat, which suits a floor that must carry more of the room’s heat. For the default room, 64 sq ft at 12 W/sq ft is 768 W, and at 15 W/sq ft 960 W.
- How much of the floor should I heat?
- Only the floor you stand on. Leave out cabinets, a tub, a toilet base, a shower pan and anything built in; in a bathroom that is typically 70% to 90% of the floor, less in a kitchen. The 10 × 8 ft bathroom (80 sq ft) is 64 sq ft to heat at 80%; heating all 80 sq ft would be 80 sq ft to heat and 960 W, and 192 W more for floor nobody walks on. You can also enter each fixture as an area to leave out and choose 100%.
- How many amps does a heated floor draw?
- Amps = watts ÷ volts. The default bathroom is 768 W, so 6.4 A at 120 V and 3.2 A at 240 V. A bigger floor adds up fast: a 20 × 20 ft room heated at 90% is 360 sq ft to heat, which is 4,320 W and 36 A at 120 V (more than one 15 A thermostat) or 18 A at 240 V.
- What size breaker does a heated floor need?
- Fixed electric space heating is a continuous load, so the circuit and breaker must carry 125% of the current (NEC Article 424, the same rule as for an electric garage heater). The default floor draws 6.4 A, times 1.25 is 8 A, so a 15 A breaker. A full 15 A thermostat load needs a 20 A breaker (15 × 1.25 = 18.75). SunTouch’s wiring table pairs up to 12 A with 14 AWG wire on a 15 or 20 A breaker and up to 15 A with 12 AWG on a 20 A breaker. Floor heat usually needs its own circuit and a GFCI; ask an electrician.
- How many thermostats do I need?
- One per 15 A of load, each on its own circuit. SunTouch’s SunStat and Schluter’s DITRA-HEAT-E-R are 15 A, which SunTouch states as 150 sq ft of 12 W/sq ft mat at 120 V or 300 sq ft at 240 V. A 20 × 20 ft room heated at 90% (360 sq ft, 36 A at 120 V) needs 3 thermostats at 120 V, or 2 at 240 V even with a 15 W/sq ft mat (22.5 A). Schluter sells a power module so one control point can run loads over 15 A.
- Should I use 120 V or 240 V?
- Both give the same heat for the same watts per square foot. The difference is current: 240 V draws half the amps, so one thermostat carries twice the floor (300 sq ft instead of 150 at 12 W/sq ft) and the wire can be smaller. The default floor is 6.4 A at 120 V and 3.2 A at 240 V. A 120 V mat is simpler for a small bathroom, since a 15 A or 20 A 120 V circuit is usually there; choose 240 V for a large floor, and buy the mat in the voltage you will wire, as the two cannot be swapped.
- How much does it cost to run a heated floor?
- Cost = kW × hours at full power × rate. The default floor is 0.77 kW, so 6 hours at 18 cents per kWh is $0.83 a day and $24.88 over 30 days. Run it 12 hours at 30 cents and it is $2.76 a day, $82.94 a month. The thermostat cycles the mat, so a floor set on for many hours uses full power for only part of them, and a programmable thermostat that warms the floor before you wake cuts the hours. The electricity cost calculator on this site does the same sum for any appliance.
- Is radiant floor heat enough to heat a room?
- Usually not on its own. The default floor puts out about 2,621 BTU/h, comfort heat that takes the chill off tile. Whether it can heat a room depends on the room’s heat loss: use the room heat loss calculator on this site to see the BTU/h at your design temperature, and compare it with the floor’s output. In a well-insulated bathroom it can carry the load; in a cold, leaky room it is a supplement.
- Does the area under cabinets or the tub need heat?
- No. Heat under cabinets and a tub has nowhere to go and can overheat the flooring; most makers say to keep mats and cable out from under fixed fixtures and at least a few inches from walls, toilets and drains. Check your product’s manual for the exact clearance. The calculator takes these out through the share of the floor to heat or the areas you leave out.
- Can I cut a heating mat to fit?
- No. The heating element is a fixed length, and cutting it changes the resistance or breaks the circuit. Nuheat mats and Schluter cables are not cut. You cut the mesh or the backing between the runs and turn the mat around to fit a layout, and the cable is laid at a spacing that fits the area. Because of that, you order the nearest available mat size (the order is usually a little more or less than the heated area), and the watts in the maker’s catalog, not this estimate, set the real load.
- What goes under and over the heating mat?
- Mats and cables are set in thinset on a clean, flat subfloor, or on cement board, and then covered with tile and its mortar or with self-leveling compound. A flat floor matters: use the self-leveling underlayment calculator if the subfloor is out of level, and the cement board calculator for the backer. An insulation board under the mat can shorten warm-up time and cut running cost. Always check the heating resistance with a meter before, during and after the tile goes down.
- How does a 15 W/sq ft mat change the numbers?
- Everything scales by 15 ÷ 12, so the default bathroom goes from 768 W to 960 W and from 6.4 A to 8 A at 120 V, and the monthly cost from $24.88 to $31.10. One thermostat then covers 120 sq ft at 120 V rather than 150. A 15 W/sq ft output is a typical high-output figure, so check what your product actually offers.
Handy tools
- Electricity Cost Calculator: Check the running cost with your own hours, rate and days per month.
- Wire Size Calculator: Pick the wire gauge for the circuit once you know the amps and the run to the panel.