Sump Pump Size Calculator: What Size Sump Pump Do I Need?
A sump pit 18 inches across that rises 10 inches in one minute takes in 11 GPM (661 GPH): each inch of an 18 inch pit holds 1.1 gallons. Against 8 ft of vertical lift and 20 ft of horizontal pipe the total dynamic head is about 10 ft (the run adds 1 ft per 10 ft, a rule of thumb). With a 50% safety margin you need a pump that delivers 1,000 GPH at 10 ft of head. Read that figure off the pump’s own GPH-at-head curve, not the maximum on the box. Enter your pit size and rise (or the GPM), the lift, the run and the pipe size to get your own numbers.
Figures based on the sources listed belowUpdated How we calculate
1,000 GPH at 10 ft of head.
1,000 GPH at 10 ft of head
- Pump capacity needed: 1,000 GPH at 10 ft of head
- Inflow: 11 GPM = 661 GPH (10 in rise in a 18 in pit × 1.1 gal per inch; 41.7 L/min)
- Total dynamic head: 10 ft (3.05 m): 8 ft vertical lift + 2 ft friction (rule of thumb, an estimate: 1 ft per 10 ft of horizontal pipe, 20 ft run; elbows and a smaller pipe add more)
- Capacity with safety margin: 16.5 GPM = 1,000 GPH (inflow + 50%). Read the pump’s GPH-at-head curve at 10 ft: the figure on the box is usually at 0 ft
- Discharge pipe velocity: 1 1/2" Schedule 40 at 16.5 GPM: 2.6 ft/s, at or above the 2 ft/s minimum some codes set
Shopping list
- Submersible sump pump
- Sump pump check valve
- Battery backup sump pump
Your project
- Inflow measured as: Rise in the pit in one minute
- Pit diameter: 18 in
- Rise in one minute: 10 in
- Vertical lift: 8 ft
- Horizontal run: 20 ft
- Discharge pipe size: 1 1/2 inch Schedule 40 PVC
- Safety margin: 50 %
Also pick up
- Submersible sump pump
- Sump pump check valve
- Battery backup sump pump
Reopen this calculation: /calculators/sump-pump-size/?s=eyJyb29tIjp7Imxlbmd0aEZ0IjowLCJ3aWR0aEZ0IjowfSwiZGVkdWN0aW9ucyI6W10sIndhc3RlUGN0IjowLjEsInBhcmFtcyI6eyJpbmZsb3dNb2RlIjowLCJwaXREaWFtZXRlckluIjoxOCwicmlzZUluIjoxMCwiZGlyZWN0R3BtIjoxMCwibGlmdEZ0Ijo4LCJydW5GdCI6MjAsInBpcGVTaXplIjoxLCJtYXJnaW5QY3QiOjUwfX0
Saved projects
No saved projects yet.
Gallons per inch and inflow by pit diameter
| Pit diameter | Per inch of depth | 5 in rise in 1 min | 10 in rise in 1 min | 20 in rise in 1 min |
|---|---|---|---|---|
| 16 in | 0.87 gal | 4.4 GPM | 8.7 GPM | 17.4 GPM |
| 18 in | 1.1 gal | 5.5 GPM | 11 GPM | 22 GPM |
| 20 in | 1.36 gal | 6.8 GPM | 13.6 GPM | 27.2 GPM |
| 24 in | 1.96 gal | 9.8 GPM | 19.6 GPM | 39.2 GPM |
| 30 in | 3.06 gal | 15.3 GPM | 30.6 GPM | 61.2 GPM |
Total dynamic head by vertical lift and horizontal run
| Vertical lift | 10 ft run | 20 ft run | 40 ft run | 60 ft run |
|---|---|---|---|---|
| 6 ft lift | 7 ft | 8 ft | 10 ft | 12 ft |
| 8 ft lift | 9 ft | 10 ft | 12 ft | 14 ft |
| 10 ft lift | 11 ft | 12 ft | 14 ft | 16 ft |
| 12 ft lift | 13 ft | 14 ft | 16 ft | 18 ft |
Methodology & assumptions
Inflow: with the pump off, the water rises in a round pit by a measured number of inches in one minute. One inch of depth in a pit of diameter d holds π ÷ 4 × d² ÷ 231 gallons (a US gallon is 231 cubic inches), so an 18 inch pit holds 1.102 gal per inch and a 24 inch pit 1.958. Inches risen in one minute × gallons per inch is the inflow in GPM, and × 60 is GPH. For the default pit that is 10 × 1.1016 = 11.02 GPM. If you know the flow, enter it in GPM instead. Total dynamic head: vertical lift (from the pump up to the highest point of the discharge pipe) plus friction in the pipe. The calculator uses a rule of thumb, an estimate, of 1 ft of head per 10 ft of horizontal pipe, so 20 ft of run adds 2 ft to the 8 ft of lift. That shortcut assumes about 1 1/2 inch pipe; each pair of 90° elbows adds roughly another 1 to 2 ft, a smaller pipe adds more and a larger pipe less. Capacity: inflow × (1 + safety margin), converted to GPH and rounded up to the next 10. The default margin of 50% is the 1.5 factor in the Roto-Rooter method (inches risen × 60 × 1.5 = GPH needed); some guides use a smaller margin. The result is the flow you want from the pump at your head: look up the pump’s GPH at that many feet on its performance curve and pick one that delivers at least that. Pipe velocity: flow ÷ flow area in Schedule 40 PVC, using the ASTM D1785 inside diameters (1.380 in for 1 1/4 inch, 1.610 for 1 1/2, 2.067 for 2). Some state plumbing codes ask for at least 2 ft/s in sump discharge piping, so the calculator flags a pipe that runs below it at the capacity you need. What this leaves out: the actual flow depends on the model, a check valve, elbows and the pipe’s age, pit shape other than round, a pit that also receives drain water, and a storm wetter than the day you measured. This is a sizing estimate, not an engineered design, and a licensed plumber should confirm it for a pit that serves a toilet or a sewage ejector.
- SupplyHouse, “How to Size a Sump Pump” (supplyhouse.com blog): sizing from gallons per minute, total head and a margin; gallons = π × r² × height ÷ 231; total head as vertical lift plus friction; a rough allowance of 1 foot of head per 10 feet of horizontal pipe, extra head for elbows, and 1 1/2 inch PVC as the usual discharge pipe. Figures as quoted from the page; confirm against the original
- Roto-Rooter, “What size basement pump do I need for my home?” (FAQ, Sump Pumps): time how far the water rises in one minute and use inches risen × 60 × 1.5 = gallons per hour of capacity needed. Figures as quoted from the page; confirm against the original
- Minnesota Rules 4715.2440, sump pumps and ejectors (Office of the Revisor of Statutes): a calculated velocity in a sump discharge line of not less than two feet per second. Figures as quoted from the page; confirm against the original
- Wisconsin Administrative Code SPS 382.30(11), sumps and ejectors: a minimum flow velocity of 2 feet per second in forced discharge piping. Figures as quoted from the page; confirm against the original
- ASTM D1785, Standard Specification for Poly(Vinyl Chloride) (PVC) Plastic Pipe, Schedules 40, 80 and 120, as tabulated in the Engineering ToolBox “PVC and CPVC pipes dimensions”: Schedule 40 inside diameters of 1.380 in (1 1/4 inch), 1.610 in (1 1/2 inch) and 2.067 in (2 inch). Figures as quoted from the page; confirm against the original
- Zoeller Pump Company, 50 Series sales sheet (FM2958): the Model 53 sump pump is rated at 2,040 GPH at 10 ft of head, with a maximum flow of 43 GPM and a maximum head of 19.25 ft. Figures as quoted from the page; confirm against the original
- Unit definitions: a US gallon is 231 cubic inches; 1 US gal = 3.785411784 L; 1 m = 3.28084 ft.
How to size a sump pump
- Measure the inflow. With the pump off in heavy rain, measure how many inches the water rises in the pit in one minute, and note the pit diameter. Or enter the GPM if you know it.
- Measure the lift and run. Measure the vertical distance from the pump to the highest point of the discharge pipe and the length of pipe that runs horizontally to the outlet.
- Read the capacity and head. The calculator gives the inflow, the total dynamic head (lift plus 1 ft per 10 ft of run, a rule of thumb) and the pump capacity with the safety margin.
- Check the pump curve. Choose a pump whose GPH-at-head curve delivers at least that capacity at your head, rather than going by horsepower or the maximum on the box.
- Check the pipe and code. Check the discharge pipe size and local plumbing code, and have a plumber confirm the design if the pit serves a toilet or sewage ejector.
Worked examples
| Project | Result |
|---|---|
| 18 inch pit, 10 inch rise in a minute, 8 ft lift, 20 ft run, 1 1/2 inch pipe | 1,000 GPH at 10 ft of head, inflow 11 GPM |
| Same, 24 inch pit | 1,770 GPH at 10 ft of head, inflow 19.6 GPM |
| Inflow of 20 GPM entered directly | 1,800 GPH at 10 ft of head, inflow 20 GPM |
| Same as the first, 15 ft lift and 60 ft run | 1,000 GPH at 21 ft of head, inflow 11 GPM |
| Same as the first, 2 inch pipe | 1,000 GPH at 10 ft of head, 1.58 ft/s in the pipe |
| Same as the first, 25% safety margin | 830 GPH at 10 ft of head, inflow 11 GPM |
Frequently asked questions
- How do I find out what size sump pump I need?
- Three numbers: the inflow, the total dynamic head and a safety margin. With the pump off in heavy rain, measure how far the pit rises in one minute; times the gallons per inch of your pit it gives GPM. Add the vertical lift and about 1 ft of head per 10 ft of horizontal pipe, then add a margin. For the default pit (11 GPM, 10 ft of head) that is 1,000 GPH at 10 ft of head.
- How many gallons are in an inch of a sump pit?
- Gallons per inch = π ÷ 4 × diameter² ÷ 231. An 18 inch pit holds 1.1 gallons per inch and a 24 inch pit 1.96, so the same 10 inch rise is 11 GPM in the 18 inch pit and 19.6 GPM in the 24 inch one. The table on this page lists other diameters.
- How do I measure the inflow?
- Unplug the pump during or just after heavy rain (or run a hose into the pit), wait one minute and measure how far the water rose. Take the measurement in the wettest conditions you expect, not on a dry day, and keep an eye on the level so the pit does not overflow. If you cannot measure, a rough estimate is better than a pump sized for a dry day, and the safety margin is there for that.
- What is total dynamic head?
- The height the pump has to push the water, in feet: the vertical lift from the pump to the highest point of the discharge pipe plus the friction in the pipe and fittings. This page estimates the friction at 1 ft per 10 ft of horizontal pipe, a rule of thumb and an estimate. 15 ft of lift and 60 ft of run is 21 ft of head.
- Why does head matter so much?
- A pump’s flow falls as the head rises. The big GPH figure on the box is the flow with little or no lift; at your head the pump delivers less. As an illustration, Zoeller’s sales sheet lists its Model 53 at 2,040 GPH at 10 ft of head against a 43 GPM (2,580 GPH) maximum flow. Always read the GPH at your head from the curve.
- Is a 1/3 HP or a 1/2 HP pump better?
- Horsepower alone does not tell you the flow at your head: two pumps of the same horsepower can differ a lot, and a well-built 1/3 HP pump can out-pump a poorly matched 1/2 HP one. This page does not quote a typical 1/3 versus 1/2 HP flow, because a figure is only reliable from one model’s curve in a maker’s chart (Zoeller, Wayne, Liberty and others publish them). Compare the GPH each candidate delivers at your total head against the capacity needed above, and choose one with room to spare.
- How much safety margin should I add?
- The Roto-Rooter method multiplies the measured one-minute rise by 1.5, a 50% margin, which is this page’s default. At 25% the default pit needs 830 GPH at 10 ft of head; at 50% it needs 1,000 GPH at 10 ft of head. A bigger margin helps if the pit takes a lot more water in a storm than on the day you measured, or if the pump will age and the pipe will scale up. It is an estimate, not a code figure.
- Does the discharge pipe size change the pump size?
- Not the inflow, but it changes the friction and the velocity. The 1 ft per 10 ft shortcut assumes about 1 1/2 inch pipe, the usual size. A 2 inch pipe loses less head, and a 1 1/4 inch pipe more. The page also checks the velocity at the capacity needed: 2.6 ft/s in 1 1/2 inch pipe, 1.58 ft/s in 2 inch pipe. Some state plumbing codes ask for at least 2 ft/s in sump discharge piping, so a very small inflow in a large pipe is flagged, as with 6.6 GPM in 1 1/4 inch pipe (1.42 ft/s).
- What if I already know the flow in GPM?
- Switch “Inflow measured as” to GPM and enter it. 20 GPM is 1,200 GPH, and with the 50% margin the pump needs 1,800 GPH at 10 ft of head.
- My pit is not 18 or 24 inches. Can I still use this?
- Yes. Enter the inside diameter of the round pit in inches or centimetres. For a square or rectangular pit the gallons per inch are the length × width ÷ 231 in square inches; convert that to an equivalent round diameter or enter the GPM directly. Measure the inside, below any lid or liner lip.
- Do I also need a battery backup or a second pump?
- This calculator sizes one pump. A pump cannot protect against a power cut or its own failure, so many people add a backup pump or a battery system. Size a backup the same way, at the head it will work against, and ask a plumber about an alarm or a second pit if a flooded basement would be costly.
- Will a bigger pump fix a wet basement?
- Only if the pump is the limit. If the pit keeps filling because water pressure is high against the foundation, drain tile or grading is the next step: see the French drain and crawl space vapor barrier calculators. A pump that is too large for the pit also short-cycles, which wears the switch and motor.
- Is this an exact answer?
- The arithmetic is exact for the numbers entered, but the sizing is an estimate: the one-minute rise varies with the storm, the head uses a rule of thumb, and each pump has its own curve. For the 24 inch pit in the examples the capacity is 1,770 GPH at 10 ft of head. Treat the result as a starting point and check the pump curve at your head.
Handy tools
- Unit Converter: Convert GPM to litres per minute or gallons per hour, or feet of head to metres.