Pipe Volume Calculator: How Much Water Is in a Pipe?
100 ft of 3/4 in Type L copper pipe holds 2.51 US gal (9.52 L). Its inside diameter is 0.785 in, so each foot holds π ÷ 4 × 0.785² × 12 ÷ 231 = 0.0251 gallons, or 2.51 gallons per 100 ft. The water weighs about 21 lb (8.34 lb per gallon). Pick the pipe type and nominal size for up to six runs, enter each length, and add a flow rate to see the flush time.
Figures based on the sources listed belowUpdated How we calculate
2.51 US gal (9.52 L).
2.51 US gal (9.52 L)
- Litres: 9.52 L (0.34 cu ft)
- Runs: 3/4 in Copper L, 100 ft (30.48 m) = 2.51 gal (total length 100 ft (30.48 m))
- Gallons per 100 ft: 3/4 in Copper L: 2.51 gal
- Weight of the water: 21 lb (9.5 kg) at 8.34 lb/gal
- Flush time: about 30 sec at 5 gal/min
- Length of 3/4 in Copper L that holds the volume below: enter a volume in US gallons to see this
Shopping list
- Tape measure (100 ft)
- Digital caliper (to measure pipe)
- Plumbing antifreeze (RV and marine)
- Hose water flow meter
- 5 gallon bucket (to time your flow)
Your project
- Run 1: pipe type: Copper Type L
- Run 1: nominal size: 3/4 in
- Run 1: length: 100 ft
- Run 2: pipe type: Copper Type L
- Run 2: nominal size: 3/4 in
- Run 2: length: 0 ft
- Run 3: pipe type: Copper Type L
- Run 3: nominal size: 3/4 in
- Run 3: length: 0 ft
- Run 4: pipe type: Copper Type L
- Run 4: nominal size: 3/4 in
- Run 4: length: 0 ft
- Run 5: pipe type: Copper Type L
- Run 5: nominal size: 3/4 in
- Run 5: length: 0 ft
- Run 6: pipe type: Copper Type L
- Run 6: nominal size: 3/4 in
- Run 6: length: 0 ft
- Flow rate for the flush time: 5
- Flow rate unit: US gallons per minute (gal/min)
- Volume to fit, for the length it fills (optional): 0
- Volume unit: US gallons
Also pick up
- Tape measure (100 ft)
- Digital caliper (to measure pipe)
- Plumbing antifreeze (RV and marine)
- Hose water flow meter
- 5 gallon bucket (to time your flow)
Reopen this calculation: /calculators/pipe-volume/?s=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
Saved projects
No saved projects yet.
Gallons per 100 ft of pipe by nominal size and type
| Nominal size | Schedule 40 steel or PVC | Schedule 80 steel or PVC | Copper Type K | Copper Type L | Copper Type M | PEX, SDR 9 copper tube size (typical) |
|---|---|---|---|---|---|---|
| 1/2 in | 1.58 | 1.22 | 1.13 | 1.21 | 1.32 | 0.96 |
| 3/4 in | 2.77 | 2.25 | 2.26 | 2.51 | 2.68 | 1.89 |
| 1 in | 4.49 | 3.74 | 4.04 | 4.29 | 4.54 | 3.12 |
| 1-1/4 in | 7.77 | 6.66 | 6.32 | 6.53 | 6.8 | 4.66 |
| 1-1/2 in | 10.58 | 9.18 | 8.95 | 9.24 | 9.51 | 6.51 |
| 2 in | 17.43 | 15.34 | 15.66 | 16.08 | 16.47 | 11.15 |
| 2-1/2 in | 24.87 | 22.02 | 24.19 | 24.79 | 25.4 | not made |
| 3 in | 38.4 | 34.31 | 34.48 | 35.39 | 36.26 | not made |
| 4 in | 66.13 | 59.72 | 60.7 | 62.22 | 63.18 | not made |
| 5 in | 103.93 | 94.51 | 94.2 | 96.96 | 98.24 | not made |
| 6 in | 150.08 | 135.41 | 134.47 | 139.39 | 141.11 | not made |
Inside diameters used, in inches
| Nominal size | Schedule 40 steel or PVC | Schedule 80 steel or PVC | Copper Type K | Copper Type L | Copper Type M | PEX, SDR 9 copper tube size (typical) |
|---|---|---|---|---|---|---|
| 1/2 in | 0.622 | 0.546 | 0.527 | 0.545 | 0.569 | 0.485 |
| 3/4 in | 0.824 | 0.742 | 0.745 | 0.785 | 0.811 | 0.681 |
| 1 in | 1.049 | 0.957 | 0.995 | 1.025 | 1.055 | 0.875 |
| 1-1/4 in | 1.380 | 1.278 | 1.245 | 1.265 | 1.291 | 1.069 |
| 1-1/2 in | 1.610 | 1.500 | 1.481 | 1.505 | 1.527 | 1.263 |
| 2 in | 2.067 | 1.939 | 1.959 | 1.985 | 2.009 | 1.653 |
| 2-1/2 in | 2.469 | 2.323 | 2.435 | 2.465 | 2.495 | not made |
| 3 in | 3.068 | 2.900 | 2.907 | 2.945 | 2.981 | not made |
| 4 in | 4.026 | 3.826 | 3.857 | 3.905 | 3.935 | not made |
| 5 in | 5.047 | 4.813 | 4.805 | 4.875 | 4.907 | not made |
| 6 in | 6.065 | 5.761 | 5.741 | 5.845 | 5.881 | not made |
Weight of water by volume
| Volume | Litres | Pounds | Kilograms |
|---|---|---|---|
| 10 US gal | 38 L | 83.4 lb | 37.8 kg |
| 25 US gal | 95 L | 208.5 lb | 94.6 kg |
| 50 US gal | 189 L | 417 lb | 189.1 kg |
| 100 US gal | 379 L | 834 lb | 378.3 kg |
| 250 US gal | 946 L | 2,085 lb | 945.7 kg |
Methodology & assumptions
Volume = π ÷ 4 × inside diameter² × length. The inside diameter (ID) is the bore, not the nominal size: a nominal 3/4 in pipe is not 0.75 in inside. With the ID in inches and the length in feet, one foot of pipe holds π ÷ 4 × ID² × 12 cubic inches, and a US gallon is exactly 231 cubic inches, so gallons = π ÷ 4 × ID² × length × 12 ÷ 231. A US gallon is exactly 3.785411784 litres. Water weighs 8.34 lb per US gallon (62.4 lb per cubic foot ÷ 7.48 gallons per cubic foot), which is about 1 kg per litre; the weight shown is the water only, not the pipe. Inside diameters: for each type the table in the calculator is the standard outside diameter minus twice the wall. Schedule 40 and 80 steel pipe (ASME B36.10M) and PVC (ASTM D1785) share outside diameters and wall thicknesses, so they share an ID; for PVC the standard gives a minimum wall, and real pipe is a little thicker, so the true ID is a little smaller and the volume a little lower, by a few percent. Copper tube sold for plumbing (ASTM B88) has an outside diameter 1/8 in larger than its nominal size, and Types K, L and M differ only in wall thickness (K thickest, M thinnest), so a given nominal size holds the most water in Type M and the least in Type K. PEX (ASTM F876, with F877 for the systems) is made to the SDR 9 copper tube size: outside diameter 1/8 in over the nominal size, and a wall of at least one ninth of it. The PEX IDs used here are outside diameter minus twice that minimum wall, and are typical only: makers’ tubing can run a few percent smaller (for example 0.475 in for 1/2 in and 0.671 in for 3/4 in on some product data), so check the data sheet for the tubing you have, or pick custom and enter its ID. Sizes a type is not made in count as 0. Custom ID lets you enter any bore in inches or millimetres. Runs: each run is a type, size and length; the volume is the sum of the runs, and runs left at 0 ft are skipped. Lengths are entered in feet or metres with the picker beside each length. Fittings, valves, a water heater, an expansion tank and a pump hold water too and are not counted; add them from the maker’s data. Gallons per 100 ft is the volume of 100 ft of that pipe, the same formula at 100 ft, and the line under the result lists it for every pipe picked in any row. Flush time = volume ÷ the flow rate you enter, in gal/min or L/min, assuming the flow stays steady; flow drops with long runs, small pipe and low supply pressure, and a flush that must replace the water several times, or push out a fluid such as antifreeze mixed with water, takes longer, so treat it as the time to move one pipe volume. Reverse: the length of run 1’s pipe that holds a volume is volume ÷ the gallons per foot of that pipe. This calculator is about the volume of water only; it does not size pipe for flow, pressure or code, and the volume of antifreeze to buy depends on the product and its label.
- Engineers Edge, Schedule 40 Steel Pipe Sizes and Dimensions (ASME/ANSI B36.10 / B36.19): wall thickness and inside diameter for nominal sizes 1/2 in to 6 in, for example 0.622 in for 1/2 in and 6.065 in for 6 in
- Engineers Edge, Schedule 80 Steel Pipe Sizes and Dimensions (ASME/ANSI B36.10 / B36.19): for example 0.546 in for 1/2 in, 1.939 in for 2 in and 5.761 in for 6 in
- Engineering ToolBox, ASTM D1785 and ASTM F441, PVC and CPVC Pipes Schedule 40 and 80: outside diameters and minimum wall thicknesses (for example 2 in Schedule 40: 2.375 in OD, 0.154 in wall, 2.067 in ID); the PVC IDs here are OD minus twice the minimum wall, and the Schedule 80 minimum walls (for example 0.179 in for 1 in and 0.432 in for 6 in) reproduce the Schedule 80 IDs in the table. A search found no copy of ASTM D1785 itself
- Copper Development Association, Copper Tube Handbook, Dimensions and Physical Characteristics of Copper Tube: Type K, Type L and Type M (tables 2a, 2b and 2c, the ASTM B88 sizes): outside diameter, wall and inside diameter; for example Type L inside diameters of 0.545, 0.785, 1.025, 1.265 and 1.505 in for 1/2 to 1-1/2 in
- Engineering ToolBox, ASTM B88 Seamless Copper Water Tubes, Dimensions: outside diameter 1/8 in over the nominal size and the Type K, L and M walls and IDs (for example Type K 1/2 in: 0.049 in wall, 0.527 in ID). The 2-1/2 to 6 in rows were checked against Engineers Edge and Wikipedia copper tube charts, which agree
- Engineering ToolBox, ASTM F876 PEX Tube, Dimensions (SDR 9, copper tube size): average outside diameter, minimum wall (0.070, 0.097, 0.125 in for 1/2, 3/4 and 1 in) and inside diameter (0.681 in for 3/4 in, 0.875 in for 1 in, 1.069 in for 1-1/4 in). PEX Universe, PEX Tubing Technical Specs, lists 0.485 in for 1/2 in; Uponor AquaPEX listings give 0.475 in for 1/2 in and 0.671 in for 3/4 in, so PEX IDs are typical, not exact. The 1-1/2 and 2 in IDs apply the SDR 9 rule (wall = OD ÷ 9) to the 1.625 and 2.125 in outside diameters and are estimates
- NIST Handbook 44, Appendix C, General Tables of Units of Measurement: the US gallon is 231 cubic inches, 3.785411784 litres
- Geometry: the volume of a cylinder, π ÷ 4 × diameter² × length. The weight of water, 8.34 lb per US gallon, is the common figure for water near room temperature (62.4 lb per cubic foot), an estimate that varies slightly with temperature
How to calculate the volume of water in a pipe
- Pick the pipe type and size. For each run choose steel or PVC Schedule 40 or 80, copper Type K, L or M, PEX, or a custom inside diameter, and the nominal size marked on the pipe.
- Enter each length. Enter the length of each run in feet or metres. Use up to six runs for a mix of sizes; leave unused runs at 0.
- Read the volume. The calculator multiplies π ÷ 4 × inside diameter² by the length and converts to US gallons and litres, with the weight of the water.
- Add a flow rate. Enter a flow in gal/min or L/min to see how long one pipe volume takes to flush.
- Or work backwards. Enter a volume to see the length of run 1’s pipe that holds it.
Worked examples
| Project | Result |
|---|---|
| 100 ft of 3/4 in Type L copper | 2.51 US gal (9.52 L), 2.51 gal per 100 ft |
| House: 40 ft of 3/4 in PEX and 120 ft of 1/2 in PEX, flushed at 4 gal/min | 1.91 US gal (7.22 L), about 29 sec at 4 gal/min |
| Heating loop: 150 ft of 1 in, 80 ft of 3/4 in and 60 ft of 1/2 in Type L copper | 9.17 US gal (34.7 L), about 76 lb of water |
| 200 ft of 2 in Schedule 40 PVC (irrigation main), flushed at 30 gal/min | 34.9 US gal (132 L), about 1 min at 30 gal/min |
| The same 200 ft in Schedule 80 | 30.7 US gal (116 L), less water because the wall is thicker |
| 50 m of 1/2 in PEX (about 164 ft) | 1.57 US gal (5.96 L) |
| 100 ft with a custom 1.25 in inside diameter | 6.37 US gal (24.1 L) |
| 100 ft of 3/4 in Type L copper flushed at 20 L/min | 2.51 US gal (9.52 L), about 29 sec at 20 L/min |
Frequently asked questions
- How do I calculate the volume of water in a pipe?
- Volume = π ÷ 4 × inside diameter² × length. Use the inside diameter, not the nominal size. For 100 ft of 3/4 in Type L copper (ID 0.785 in): π ÷ 4 × 0.785² = 0.484 sq in, × 1,200 in = 581 cu in, ÷ 231 cu in per gallon = 2.51 US gal (9.52 L).
- How many gallons are in 100 feet of pipe?
- It depends on the size and type. 100 ft of 1/2 in Schedule 40 holds 1.58 gallons, 3/4 in 2.77, 1 in 4.49, 2 in 17.43 and 4 in 66.13. The first table on this page lists gallons per 100 ft for every size and type.
- Why is nominal size not the inside diameter?
- Nominal size is a name. Steel and PVC pipe keep the same outside diameter for every schedule and make the wall thicker, so the bore shrinks: a 2 in pipe is 2.067 in inside in Schedule 40 and 1.939 in in Schedule 80. Copper tube is 1/8 in larger outside than its nominal size, and its bore depends on the type, K, L or M. Because volume goes with the square of the diameter, a small difference matters: 200 ft of 2 in pipe holds 34.9 US gal (132 L) in Schedule 40 and 30.7 US gal (116 L) in Schedule 80.
- Does copper Type K, L or M hold more water?
- Type M has the thinnest wall and so the biggest bore: for 3/4 in, 100 ft holds 2.68 gallons in Type M, 2.51 in Type L and 2.26 in Type K. The gap is largest in the small sizes: Type M holds about 18% more than Type K at 3/4 in and about 5% more at 2 in.
- How much water is in my PEX?
- 100 ft of 1/2 in PEX holds about 0.96 gallons and 3/4 in about 1.89. PEX is the least certain of the types here: the standard fixes the outside diameter and a minimum wall, and real tubing has a thicker wall than the minimum, so makers’ IDs run a few percent smaller than the ones used here (0.475 in for 1/2 in and 0.671 in for 3/4 in on some product data, against 0.485 and 0.681). That is a difference of about 4% in volume for 1/2 in. Check the data sheet, or use custom and enter the ID.
- How do I work out the flush time?
- Volume ÷ flow rate. A house with 40 ft of 3/4 in and 120 ft of 1/2 in PEX holds 1.91 US gal (7.22 L), so at 4 gal/min one pipe volume takes about 29 sec. In litres, 100 ft of 3/4 in Type L at 20 L/min takes about 29 sec. Real flow falls in long, narrow runs, so this is a minimum for moving one pipe volume; to flush several volumes, multiply.
- How much antifreeze do I need to fill a loop?
- Start from the volume of the loop: 150 ft of 1 in, 80 ft of 3/4 in and 60 ft of 1/2 in Type L copper holds 9.17 US gal (34.7 L). Add the volume of the boiler, heat exchanger, tank and fittings from their data sheets, which the calculator does not count, then follow the antifreeze label for the mix ratio. To fill a loop you only need the antifreeze share of that volume, not all of it.
- How long a pipe holds a given volume?
- Divide the volume by the gallons per foot of the pipe. Enter the volume in run 1’s “volume to fit” field and the calculator does it for the type and size in run 1. 5 US gallons fills 116.64 ft (35.55 m) of 1 in Type L copper, and 20 litres fills 123.26 ft.
- How much does the water in a pipe weigh?
- About 8.34 lb per US gallon (1 kg per litre), so the 2.51 US gal (9.52 L) in the 100 ft of 3/4 in Type L copper weighs about 21 lb. That is the water alone; add the pipe, which for a long run of large steel pipe can weigh more than the water.
- How do I enter a pipe that is not in the list?
- Pick “Custom inside diameter” for the run and enter the bore in inches or mm from the pipe’s data sheet or a caliper reading. 100 ft with an inside diameter of 1.25 in holds 6.37 US gal (24.1 L). This is also the way to use makers’ own PEX or PVC dimensions, or pipe of another standard such as PE or CPVC.
- Can I enter lengths in metres?
- Yes: each length has an ft/m picker beside it. 50 m of 1/2 in PEX (about 164.04 ft) holds 1.57 US gal (5.96 L). Volumes are shown in US gallons and litres together.
- Does the calculator include fittings, valves or tanks?
- No. It counts straight pipe only. Fittings add a little, and a water heater, expansion tank, pump or boiler holds far more; take their volumes from their data sheets and add them.
Handy tools
- Unit Converter: Convert the result between gallons, litres and cubic feet, or a length between feet and metres.
- Volume Calculator: Volume of a cylinder or any other solid, such as a tank, in cubic feet, litres and gallons.