HVAC Airflow (CFM) Calculator: CFM per Ton, per Room and ACH
A 3 tons air conditioner at the usual rule of thumb of 400 CFM per ton moves 1,200 CFM of air. Split among five rooms by their cooling loads (9,000, 6,000, 6,500, 5,000 and 3,500 BTU/h, 30,000 in all), that is room 1 360 CFM, room 2 240 CFM, room 3 260 CFM, room 4 200 CFM, room 5 140 CFM. A system with a sensible capacity of 27,000 BTU/h at that airflow cools the air by about 20.8°F. The 400 CFM per ton figure is a rule of thumb (350 to 450 depending on climate), and the room split is the proportional method of ACCA Manual D. The real design comes from a Manual J load calculation and the equipment’s data sheet.
Figures based on the sources listed belowUpdated How we calculate
1,200 CFM.
1,200 CFM
- System airflow: 3 tons × 400 CFM per ton (rule of thumb)
- Room 1 supply: 360 CFM (9,000 BTU/h, 30% of 30,000 BTU/h)
- Room 2 supply: 240 CFM (6,000 BTU/h, 20% of 30,000 BTU/h)
- Room 3 supply: 260 CFM (6,500 BTU/h, 21.7% of 30,000 BTU/h)
- Room 4 supply: 200 CFM (5,000 BTU/h, 16.7% of 30,000 BTU/h)
- Room 5 supply: 140 CFM (3,500 BTU/h, 11.7% of 30,000 BTU/h)
- Supply air temperature drop: 20.8°F below the return air, so about 54.2°F supply (27,000 ÷ (1.08 × 1,200))
- Air changes per hour: 4.46 ACH (100 CFM × 60 ÷ 1,344 cu ft)
- CFM for the target ACH: 135 CFM (6 ACH × 1,344 cu ft ÷ 60)
Shopping list
- Anemometer / airflow meter
- Digital thermometer (supply and return)
- Foil duct tape (UL 181)
- Furnace filter
- Bathroom exhaust fan
Your project
- System size: 3 tons of cooling
- Airflow per ton (CFM): 400 CFM per ton (typical)
- Rooms are entered as: Load in BTU/h (Manual J room loads)
- Room 1 load (BTU/h) or area (sq ft): 9,000
- Room 2 load (BTU/h) or area (sq ft): 6,000
- Room 3 load (BTU/h) or area (sq ft): 6,500
- Room 4 load (BTU/h) or area (sq ft): 5,000
- Room 5 load (BTU/h) or area (sq ft): 3,500
- Room 6 load (BTU/h) or area (sq ft): 0
- Room 7 load (BTU/h) or area (sq ft): 0
- Room 8 load (BTU/h) or area (sq ft): 0
- Sensible cooling capacity: 27,000 BTU/h
- Return air temperature: 75 °F
- Room length (for air changes): 14 ft
- Room width (for air changes): 12 ft
- Ceiling height (for air changes): 8 ft
- Airflow into or out of the room: 100 CFM
- Target air changes per hour: 6 ACH
Also pick up
- Anemometer / airflow meter
- Digital thermometer (supply and return)
- Foil duct tape (UL 181)
- Furnace filter
- Bathroom exhaust fan
Reopen this calculation: /calculators/hvac-cfm/?s=eyJyb29tIjp7Imxlbmd0aEZ0IjowLCJ3aWR0aEZ0IjowfSwiZGVkdWN0aW9ucyI6W10sIndhc3RlUGN0IjowLjEsInBhcmFtcyI6eyJ0b25zIjozLCJjZm1QZXJUb24iOjQwMCwiYmFzaXMiOjAsInJvb20xIjo5MDAwLCJyb29tMiI6NjAwMCwicm9vbTMiOjY1MDAsInJvb200Ijo1MDAwLCJyb29tNSI6MzUwMCwicm9vbTYiOjAsInJvb203IjowLCJyb29tOCI6MCwic2Vuc2libGVCdHUiOjI3MDAwLCJyZXR1cm5UZW1wRiI6NzUsImFjaExlbmd0aEZ0IjoxNCwiYWNoV2lkdGhGdCI6MTIsImFjaEhlaWdodEZ0Ijo4LCJhY2hDZm0iOjEwMCwidGFyZ2V0QWNoIjo2fX0
Saved projects
No saved projects yet.
System airflow by tonnage (rule of thumb)
| System size | 350 CFM per ton (humid) | 400 CFM per ton (typical) | 450 CFM per ton (dry) |
|---|---|---|---|
| 1.5 tons | 525 CFM | 600 CFM | 675 CFM |
| 2 tons | 700 CFM | 800 CFM | 900 CFM |
| 2.5 tons | 875 CFM | 1,000 CFM | 1,125 CFM |
| 3 tons | 1,050 CFM | 1,200 CFM | 1,350 CFM |
| 3.5 tons | 1,225 CFM | 1,400 CFM | 1,575 CFM |
| 4 tons | 1,400 CFM | 1,600 CFM | 1,800 CFM |
| 5 tons | 1,750 CFM | 2,000 CFM | 2,250 CFM |
Local exhaust minimums for bathrooms and kitchens
| Room | Intermittent (on demand) | Continuous (ASHRAE 62.2) | Continuous (IRC) |
|---|---|---|---|
| Bathroom or toilet room | 50 CFM | 20 CFM | 20 CFM |
| Kitchen | 100 CFM | 5 air changes per hour of the kitchen volume | 25 CFM |
CFM needed for a target number of air changes per hour
| Room | Volume (cu ft) | 4 ACH | 6 ACH | 8 ACH |
|---|---|---|---|---|
| Bathroom, 8 × 5 × 8 ft | 320 | 22 CFM | 32 CFM | 43 CFM |
| Bedroom, 12 × 12 × 8 ft | 1,152 | 77 CFM | 116 CFM | 154 CFM |
| Living room, 15 × 20 × 8 ft | 2,400 | 160 CFM | 240 CFM | 320 CFM |
Sensible heat moved by an airflow and temperature drop
| Airflow | ΔT 15°F | ΔT 18°F | ΔT 20°F | ΔT 22°F |
|---|---|---|---|---|
| 800 CFM | 12,960 BTU/h | 15,552 BTU/h | 17,280 BTU/h | 19,008 BTU/h |
| 1,000 CFM | 16,200 BTU/h | 19,440 BTU/h | 21,600 BTU/h | 23,760 BTU/h |
| 1,200 CFM | 19,440 BTU/h | 23,328 BTU/h | 25,920 BTU/h | 28,512 BTU/h |
| 1,600 CFM | 25,920 BTU/h | 31,104 BTU/h | 34,560 BTU/h | 38,016 BTU/h |
Methodology & assumptions
This page does four separate calculations. None is a duct design: ducts are sized from the room airflows, the friction rate and the fittings by ACCA Manual D, and the loads come from ACCA Manual J. 1) System airflow = tons × CFM per ton. The usual rule of thumb is 400 CFM per ton of cooling, which is also the airflow most manufacturers assume when they rate residential equipment. ACCA’s own technical writing notes that the right figure moves with relative humidity, temperatures, air density and elevation, and that in a hot, humid climate a lower airflow such as 350 CFM per ton can keep occupants more comfortable, while dry climates use up to 450. This tool offers 350, 400 and 450 CFM per ton; other guides give wider ranges, such as 300 to 350 for humid and 450 to 550 for dry climates, so treat all of it as an estimate. The blower speed you can actually set, the static pressure in the ducts, the filter and the coil all change the real airflow: the manufacturer’s blower table and a measured airflow govern. A ton is 12,000 BTU/h of cooling. 2) Room airflow, the proportional method: room CFM = system CFM × room load ÷ total load. Manual D takes each room’s airflow from the room’s heating or cooling load, so a room carrying 20% of the load gets 20% of the air. Enter the room loads from a Manual J report in BTU/h. If you have no loads, you can enter floor areas instead: that is a simple area share and is approximate, because two rooms of the same size can have very different loads (a west-facing room with big windows against an interior bedroom), so use it only to get a first idea. Rooms left at 0 are left out; up to 8 rooms are supported. The room figures are rounded to whole CFM, so they may differ from the system figure by a CFM or two. Where heating and cooling loads give different splits, Manual D uses the larger airflow for the room, a step this tool does not do. 3) Supply temperature check: sensible heat Q (BTU/h) = 1.08 × CFM × ΔT (°F). The constant comes from standard air: 0.075 lb per cu ft × 0.24 BTU/lb·°F × 60 min per hour = 1.08. It is for sensible heat only (a change in dry-bulb temperature, not moisture) and for standard air at sea level; at altitude or with very warm or humid air the constant is lower. Rearranged, ΔT = Q ÷ (1.08 × CFM), and the supply temperature is the return temperature less ΔT. Use the equipment’s sensible capacity from its data sheet at your conditions, not the nameplate total, which includes the latent (moisture) part. 4) Air changes per hour: ACH = CFM × 60 ÷ room volume in cu ft, and the CFM needed for a target is ACH × volume ÷ 60. Room volume = length × width × ceiling height. For a supply register, the CFM is the airflow the register delivers; for a fan, the rated airflow at its installed duct resistance, which is less than the number on the box if the duct is long. ACH counts air moved through the room, not how well it is mixed, and it is not a ventilation requirement by itself. The exhaust rates in the table (bathroom and kitchen) are the local exhaust minimums in ASHRAE 62.2 and the International Residential Code; whole-dwelling ventilation under ASHRAE 62.2 is a separate calculation from floor area and bedrooms, Qtot = 0.03 × floor area (sq ft) + 7.5 × (bedrooms + 1) CFM, which is not computed here. Codes are adopted and amended locally: check the edition your jurisdiction uses.
- ACCA blog (HVAC Blog), “400 CFM Per Ton, Or Is It?”: many factors, including relative humidity, dry-bulb and wet-bulb temperatures, air density and elevation, change the typical 400 CFM per ton; in hot, humid climates a lower airflow such as 350 CFM per ton can keep occupants comfortable and in dry climates 450 CFM per ton gives more sensible capacity; not checked against the full page
- GreenBuildingAdvisor, “Getting the Right Airflow for an Air Conditioner”: 400 cfm per ton as the nominal figure, with 300 to 350 for humid and 450 to 550 for dry climates described as guides, not hard limits
- RESNET (2013), Spohn, “Airflow” presentation summarising ENERGY STAR guidance: ideal airflow 400 cfm per ton, with systems under 350 cfm per ton needing correction. A slide deck, so the current ENERGY STAR specification may differ
- ACCA, Manual D, Residential Duct Systems (ANSI/ACCA 1 Manual D): room airflow comes from the Manual J room loads, divided in proportion to the load. The formula as written here was checked against secondary descriptions (a GreenBuildingAdvisor Q&A, “Guidance calculating room CFM requirements based on heat load”, which describes dividing the blower airflow in proportion to each room’s load); the manual itself is not free to read, so check it for design work
- ACCA blog, “The Physics of Heat and Air Flow”, and HVAC School, “Sensible Heat in Air and Water”: Q = 1.08 × CFM × ΔT for standard air, from 0.075 lb/cu ft × 0.24 BTU/lb·°F × 60 min/h, sensible heat only
- ASHRAE Standard 62.2, Ventilation and Acceptable Indoor Air Quality in Residential Buildings: whole-building rate Qtot = 0.03 × floor area + 7.5 × (bedrooms + 1) in I-P units (equation 4.1a, seen in the addenda ASHRAE publishes), and the local exhaust rates, bathroom 50 CFM intermittent or 20 CFM continuous and kitchen 100 CFM intermittent or 5 air changes per hour continuous (as given in a RESNET introduction to the standard and the Addendum m table; the current edition was not read directly)
- International Residential Code (2021), section M1505.4.4 (Table M1507.4 in the 2015 edition), local exhaust: bathroom 50 CFM intermittent or 20 CFM continuous, kitchen 100 CFM intermittent or 25 CFM continuous. Section numbers and values depend on the edition adopted; check your jurisdiction’s code. Found in code-text excerpts and a building-department guide, not in the ICC text itself
How to work out HVAC airflow in CFM
- Find the system airflow. Multiply the system size in tons by about 400 CFM per ton (350 for a hot, humid climate, 450 for a dry one). 12,000 BTU/h is one ton.
- Split it by room. Enter each room’s load in BTU/h, or its floor area in sq ft as an approximation. Each room gets the system CFM times its load divided by the total load.
- Check the supply temperature. Divide the equipment’s sensible capacity in BTU/h by 1.08 times the CFM to get the temperature drop, and subtract it from the return air temperature.
- Find air changes per hour. Multiply the room’s length, width and ceiling height to get its volume in cubic feet. ACH is the CFM times 60 divided by that volume.
- Find the CFM for a target. Multiply the ACH you want by the volume and divide by 60 to get the CFM a register or fan has to move.
Worked examples
| Project | Result |
|---|---|
| 3-ton system at 400 CFM per ton, five rooms by load | 1,200 CFM in all: room 1 360 CFM, room 2 240 CFM, room 3 260 CFM, room 4 200 CFM, room 5 140 CFM |
| The same 3 tons in a hot, humid climate (350 CFM per ton) | 1,050 CFM |
| The same 3 tons in a dry climate (450 CFM per ton) | 1,350 CFM |
| 1.5-ton system, three rooms of 8,000, 6,000 and 4,000 BTU/h | 600 CFM in all: room 1 267 CFM, room 2 200 CFM, room 3 133 CFM; supply drop 20.8°F at 13,500 BTU/h sensible |
| 2 tons over rooms of 400, 250 and 150 sq ft (area share, approximate) | 800 CFM in all: room 1 400 CFM, room 2 250 CFM, room 3 150 CFM |
| Bathroom 8 × 5 × 8 ft with a 50 CFM fan, target 8 ACH | Bathroom volume 320 cu ft: 9.38 ACH at 50 CFM, and 8 ACH needs 43 CFM (page default system: 1,200 CFM) |
| 3 tons with 36,000 BTU/h sensible capacity at 1,200 CFM | 1,200 CFM: a 27.8°F drop, about 47.2°F supply from a 75°F return |
Frequently asked questions
- How many CFM per ton does an air conditioner need?
- The usual rule of thumb is 400 CFM per ton of cooling, so a 3 tons system moves 1,200 CFM. Hot, humid climates often run lower, about 350 CFM per ton (1,050 CFM for 3 tons), to remove more moisture, and dry climates higher, about 450 (1,350 CFM). These are rules of thumb and estimates: the equipment’s data sheet, the blower speed you can set and a measured airflow decide the real figure.
- How do I find the CFM for each room?
- Use the proportional method from ACCA Manual D: room CFM = system CFM × room load ÷ total load. In the example above the five rooms carry 30%, 20%, 21.7%, 16.7%, 11.7% of the 30,000 BTU/h load, so the 1,200 CFM splits into room 1 360 CFM, room 2 240 CFM, room 3 260 CFM, room 4 200 CFM, room 5 140 CFM. The room loads come from a Manual J calculation.
- What if I do not have room loads?
- Enter the floor areas instead and switch the entry to sq ft. The calculator then gives each room its share of the floor area. That is approximate: it ignores windows, sun and exposure, so a sunny room with a lot of glass will be underserved. For example 2 tons over rooms of 400, 250 and 150 sq ft gives room 1 400 CFM, room 2 250 CFM, room 3 150 CFM from 800 CFM. Use it as a starting guess, and get room loads from a Manual J calculation for a real design.
- How do I calculate air changes per hour (ACH)?
- ACH = CFM × 60 ÷ room volume in cubic feet. A 14 × 12 × 8 ft room is 1,344 cu ft, so 100 CFM through it is 4.46 ACH. To reach a target, CFM = ACH × volume ÷ 60: 6 ACH in that room needs 135 CFM.
- What exhaust fan size do I need for a bathroom or kitchen?
- ASHRAE 62.2 and the International Residential Code both list a bathroom exhaust fan at 50 CFM when it runs on demand (intermittent) or 20 CFM when it runs continuously, and a kitchen at 100 CFM on demand. For continuous kitchen exhaust, ASHRAE 62.2 gives 5 air changes per hour and the 2021 IRC gives 25 CFM. A bathroom of 8 × 5 × 8 ft (320 cu ft) with a 50 CFM fan changes its air 9.4 times an hour, and 8 ACH would need 43 CFM. Fan ratings are at a test pressure, and ducts reduce them. Codes vary by location and edition.
- What does 1.08 × CFM × ΔT mean?
- It is the sensible heat equation for standard air: Q (BTU/h) = 1.08 × CFM × ΔT (°F). The 1.08 is 0.075 lb per cu ft (air density) × 0.24 BTU/lb·°F (specific heat) × 60 minutes per hour. Rearranged, ΔT = Q ÷ (1.08 × CFM): 27,000 BTU/h at 1,200 CFM is a 20.8°F drop, so a 75°F return becomes about 54.2°F supply. It covers sensible heat only and is for standard air at sea level.
- What if the supply temperature drop looks wrong?
- A drop much smaller or larger than the equipment is rated for points at the airflow. The same 3-ton system with a sensible capacity of 36,000 BTU/h at 1,200 CFM would show a 27.8°F drop. Low airflow gives a large drop and a cold coil (and, in humid climates, more moisture removal), while high airflow gives a small drop. Compare the result with the manufacturer’s data sheet; a measured temperature split (return minus supply) is one of the ways technicians check airflow.
- Is this a duct design?
- No. Duct sizing is ACCA Manual D: it takes the room airflows, the available static pressure and the length and fittings of each run and returns duct sizes. Cooling loads come from ACCA Manual J, and equipment selection from Manual S. This page gives a first idea of airflow, not a design, so use a contractor or those manuals for new duct work.
- Why do the room CFM values not add up to the system CFM?
- Each room is rounded to the nearest whole CFM, so the room figures can be one or two CFM off the system total. The exact shares always add to the system airflow.