Bathroom Exhaust Fan Size Calculator (CFM)

A 10 × 8 ft bathroom is 80 sq ft, and the Home Ventilating Institute (HVI) method for a bathroom of 100 sq ft or less is 1 CFM per square foot, so it needs a fan of 80 CFM (never under 50 CFM). With 10 ft of duct and two elbows the airflow you actually get is less than the number on the box, so shop for about 90 CFM (a typical estimate). Over 100 sq ft the HVI method switches to fixtures: 50 CFM for each toilet, shower and tub and 100 CFM for a jetted tub. A ceiling over 8 ft raises the figure (room volume × 8 air changes per hour ÷ 60), and the International Residential Code floor is 50 CFM on demand or 20 CFM continuous.

Figures based on the sources listed belowUpdated How we calculate

Over 8 ft, the room volume at 8 air changes per hour is also worked and the larger figure is used.

The fixture method applies to bathrooms over 100 sq ft. An enclosed toilet compartment should have its own fan.

Ordinary tubs, 50 CFM each. A shower over a tub counts as both.

100 CFM each in the HVI fixture method.
About 4 in is typical up to 100 CFM, 6 in from 100 to 200 CFM. A rule of thumb: the fan’s installation sheet governs.

Straight length from the fan to the outside cap, in feet.

Each 90° elbow is counted as about 5 ft of extra duct, a typical estimate.

80 CFM.

80 CFM

  • HVI method: 80 CFM: 80 sq ft at 1 CFM per sq ft, minimum 50 CFM
  • Fixture method: 100 CFM (2 toilet, shower or tub at 50 CFM each, jetted tubs at 100 CFM), used only above 100 sq ft
  • Ceiling height check: 640 cu ft × 8 ACH ÷ 60 = 86 CFM, applied only over 8 ft
  • Code minimum (IRC): 50 CFM on demand or 20 CFM continuous; this size meets it
  • Fan rating to shop for: 90 CFM: 20 ft of equivalent duct costs about 10% of the airflow (typical estimate)
  • Duct size: 4 in duct is enough for a 90 CFM fan (about 4 in is typical)
  • Noise (sones): look for 1.0 sone or less for a quiet fan; 2.0 or less is common (typical, lower is quieter)

Shopping list

  • Bathroom exhaust fan, 80 CFM
  • Bathroom fan with humidity sensor
  • Insulated flexible duct, 4 in
  • Roof or wall vent cap, 4 in
  • Foil duct tape (UL 181)
Show diagram

Saved projects

No saved projects yet.

Fan size for common bathrooms

Worked by this calculator for an 8 ft ceiling and a toilet and shower: the HVI figure, and the rating to shop for with 10 ft of duct and two elbows (a typical estimate: 10% derating).
BathroomSq ftHVI sizeRating to shop for
Powder room, 5 × 4 ft2050 CFM60 CFM
Half bath, 6 × 5 ft3050 CFM60 CFM
Guest bath, 8 × 5 ft4050 CFM60 CFM
Full bath, 10 × 8 ft8080 CFM90 CFM
Large bath, 10 × 10 ft100100 CFM115 CFM

Fan size by fixtures for bigger bathrooms

The HVI fixture method for rooms over 100 sq ft: 50 CFM per toilet, shower and tub, 100 CFM per jetted tub. Worked by this calculator with an 8 ft ceiling.
FixturesSq ftFixture totalSize used
Toilet and shower112100 CFM100 CFM
Toilet, shower and tub140150 CFM150 CFM
Toilet and shower, 12 × 12 ft144100 CFM100 CFM
Toilet, shower and jetted tub168200 CFM200 CFM
Two toilets, two showers and a jetted tub224300 CFM300 CFM

Fan size by ceiling height

CFM needed (HVI figure or room volume × 8 air changes per hour ÷ 60, whichever is larger over 8 ft), for a toilet and shower. Worked by this calculator.
Bathroom8 ft ceiling9 ft ceiling10 ft ceiling12 ft ceiling
5 × 8 ft50 CFM50 CFM54 CFM64 CFM
8 × 10 ft80 CFM96 CFM107 CFM128 CFM
10 × 10 ft100 CFM120 CFM134 CFM160 CFM

Duct length derating (typical estimate)

This site’s own typical estimate, not a published table: equivalent length is the straight run plus 5 ft per 90° elbow. A fan’s own performance chart is the real figure.
Equivalent duct lengthAirflow lostRating to shop for, 80 CFM neededRating to shop for, 110 CFM needed
up to 10 ft0%80 CFM110 CFM
11 to 25 ft10%90 CFM125 CFM
26 to 50 ft20%100 CFM140 CFM
over 50 ft30%115 CFM160 CFM

Duct size and noise (typical)

Rules of thumb from retail and installer guides, not requirements. The fan’s installation sheet governs.
Fan ratingTypical ductSones to look for
Up to 100 CFM4 in1.0 or less for quiet; 2.0 or less common
101 to 200 CFM6 in1.0 or less for quiet; 2.0 or less common
Over 200 CFM8 in or largercheck the data sheet

Local exhaust minimum for a bathroom (IRC)

International Residential Code section M1505.4.4 (2021; Table M1507.4 in the 2015 edition). Editions and local amendments differ, so check yours.
OperationMinimum exhaust
Intermittent (on demand, a switch or timer)50 CFM
Continuous20 CFM

Methodology & assumptions

This page sizes a bathroom exhaust fan in cubic feet per minute (CFM) in four steps. 1) The HVI method. The Home Ventilating Institute’s bathroom exhaust fan guidance gives a minimum of 50 CFM for a bathroom under 50 sq ft, 1 CFM per square foot of floor area for 50 to 100 sq ft, and, above 100 sq ft, the sum of the fixtures: 50 CFM for each toilet, shower and bathtub and 100 CFM for a jetted tub. HVI’s own pages are not worded identically about the 50 CFM floor (one chart applies it under 50 sq ft, other HVI text says 1 CFM per sq ft for rooms up to 100 sq ft, and the manufacturers that repeat it apply the 50 CFM minimum to all small baths), so this calculator takes the safe reading, 1 CFM per sq ft with a floor of 50 CFM for a room of up to 100 sq ft; the two readings agree from 50 sq ft up. HVI also says an enclosed toilet compartment should have its own fan and that higher rates are acceptable. A room over 100 sq ft with no fixtures entered falls back to 1 CFM per sq ft, so the answer is never blank. The fixture method is shown even when it is not used so you can compare. 2) Ceiling height. HVI’s guidance assumes a standard ceiling of about 8 ft. For a taller room this tool also works the volume method used in ventilation guides: CFM = length × width × ceiling height × air changes per hour ÷ 60, at 8 air changes per hour. The result is the larger of the HVI figure and the volume figure when the ceiling is over 8 ft; a 10 × 8 ft bathroom with a 10 ft ceiling is 800 cu ft, and 800 × 8 ÷ 60 is 107 CFM. The 8 air changes per hour is a common rule of thumb in ventilation guides rather than an HVI or code requirement; air changes per hour are covered on the HVAC airflow (CFM) page here. 3) Code. The International Residential Code (section M1505.4.4 in the 2021 edition, Table M1507.4 in the 2015 edition) lists a bathroom or toilet room at 50 CFM when the fan runs on demand (intermittent) or 20 CFM when it runs continuously, and the same figures are in ASHRAE 62.2. This is a minimum for the fan’s rated airflow, and the section and table numbers depend on the edition your area adopted, so check yours; local codes can be stricter. The HVI method gives at least 50 CFM, so it never falls under the on-demand code minimum. 4) Duct. A fan’s CFM on the box is measured at a test pressure (often 0.1 in. of water, with ENERGY STAR listings at 0.25 in.) while a real installation usually has more resistance, and the longer, smaller and more twisted the duct, the more airflow is lost. There is no standard derating table, so this tool uses its own typical estimate: add 5 ft of equivalent straight duct per 90° elbow to the run, then assume 0% loss up to 10 ft, 10% from 11 to 25 ft, 20% from 26 to 50 ft and 30% over 50 ft, and divide the needed CFM by what is left (rounded up to the next 5 CFM). Flexible duct, 3 in duct and a roof cap lose more. The only reliable figure is the fan’s own pressure-versus-airflow chart from its manufacturer, so use that for a long or complicated run. Duct size: retail and installer guides give about 4 in for a fan up to 100 CFM and 6 in for 100 to 200 CFM, which is how this tool flags a small duct; the fan’s installation sheet governs. Noise: fans are rated in sones (HVI-certified ratings), a scale where 1.0 sone is about a refrigerator running and a lower number is quieter; most buying guides suggest 1.0 sone or less for a quiet fan and 2.0 or less as acceptable, which are typical figures, not requirements. Humidity: HVI advises leaving the fan on for about 20 minutes after a shower. This is a sizing aid, not a ventilation design, and the fan’s ceiling or wall location, the make-up air and the local code are for you and your installer to settle. Figures are in CFM, so they do not change under the metric switch; the room fields convert between feet and metres.

How to size a bathroom exhaust fan

  1. Measure the bathroom. Measure the floor length and width in feet and multiply to get square feet, and note the ceiling height.
  2. Pick the HVI method. Up to 100 sq ft use 1 CFM per square foot with a minimum of 50 CFM. Over 100 sq ft add 50 CFM for each toilet, shower and tub and 100 CFM for a jetted tub.
  3. Check the ceiling. If the ceiling is over 8 ft, work length × width × height × 8 ÷ 60 and use that number if it is larger.
  4. Allow for the duct. Add about 5 ft of duct for each elbow to the run. A long, small or flexible duct loses airflow, so choose a fan rated higher than the CFM you need and check its pressure-versus-airflow chart.
  5. Choose duct size and noise. Use about 4 in duct to 100 CFM and 6 in above, and look for a fan of 1.0 sone or less. Check your local code for the 50 CFM on-demand or 20 CFM continuous minimum.

Worked examples

ProjectResult
10 × 8 ft bathroom, 8 ft ceiling, 10 ft of 4 in duct with two elbows80 CFM (80 sq ft); shop for about 90 CFM
8 × 5 ft guest bath50 CFM (40 sq ft, so the 50 CFM minimum applies)
5 × 4 ft powder room50 CFM (20 sq ft, the 50 CFM minimum)
10 × 10 ft bathroom, exactly 100 sq ft100 CFM (1 CFM per sq ft)
14 × 10 ft master bath with a toilet, shower and tub150 CFM by the fixture method (140 sq ft)
14 × 12 ft bath with a toilet, shower and jetted tub200 CFM by the fixture method (168 sq ft)
The 10 × 8 ft bathroom with a 10 ft ceiling107 CFM (800 cu ft × 8 air changes ÷ 60)
The same room with 30 ft of duct and three elbows80 CFM, shop for about 100 CFM (45 ft equivalent, 20% derating, a typical estimate); a 4 in duct is enough

Frequently asked questions

What size bathroom exhaust fan do I need?
HVI’s rule for a bathroom of 100 sq ft or less is 1 CFM per square foot of floor area, with a minimum of 50 CFM. A 10 × 8 ft bathroom is 80 sq ft, so 80 CFM; a 5 × 4 ft powder room is 50 CFM because of the 50 CFM minimum. Over 100 sq ft, add up the fixtures (50 CFM per toilet, shower and tub, 100 for a jetted tub).
How do I size a fan for a bathroom over 100 square feet?
Use the fixture method: 50 CFM for each toilet, shower and bathtub and 100 CFM for a jetted tub. A 14 × 10 ft bathroom (140 sq ft) with a toilet, a shower and a tub is 150 CFM; a 14 × 12 ft room with a toilet, a shower and a jetted tub is 200 CFM. If you enter no fixtures, this calculator falls back to 1 CFM per sq ft (120 CFM for a 12 × 10 ft room), but the fixture count is the HVI method.
Does the ceiling height change the CFM?
HVI’s rule is written for a standard ceiling of about 8 ft. For a taller room, work the volume: length × width × height × 8 air changes per hour ÷ 60. A 10 × 8 ft room with a 10 ft ceiling is 800 cu ft, so 800 × 8 ÷ 60 gives 107 CFM, against 80 CFM at 8 ft. The calculator uses the larger of the two figures over 8 ft. The 8 air changes per hour is a common ventilation-guide rule of thumb, not an HVI or code figure.
What does the building code require?
The International Residential Code (section M1505.4.4 in the 2021 edition, Table M1507.4 in 2015) lists a bathroom or toilet room at 50 CFM for a fan that runs on demand or 20 CFM for one that runs continuously. ASHRAE 62.2 has the same local exhaust figures. These are minimums for the fan’s rated airflow; the HVI method gives at least 50 CFM, so it never falls under the on-demand figure. Codes are adopted and amended locally.
What if my bathroom is exactly 100 square feet?
Up to and including 100 sq ft the 1 CFM per square foot rule applies, so a 10 × 10 ft bathroom is 100 CFM. At 101 sq ft the HVI method switches to fixtures, and a toilet and shower give 100 CFM, which is about the same. The two rules meet around this size on purpose.
Why does the calculator say to shop for a bigger fan than the CFM?
A fan’s box rating is measured at a test pressure with little duct resistance. A longer run, more elbows, flexible duct or a small duct cut the airflow you actually get. There is no standard derating table, so this page uses its own typical estimate (0% to 10 ft of equivalent duct, 10% to 25 ft, 20% to 50 ft, 30% beyond), with each elbow counted as 5 ft. For the default 10 × 8 ft room with 10 ft of duct and two elbows, 80 CFM becomes about 90 CFM; with 30 ft of duct and three elbows (45 ft equivalent) it becomes 100 CFM. A fan’s own pressure-versus-airflow chart is the real answer.
What duct size should I use for a bathroom fan?
Retail and installer guides give about 4 in duct for a fan up to 100 CFM and 6 in for a 100 to 200 CFM fan, and many bigger fans are made for 6 in only. A bigger duct is never a mistake, since it lowers resistance; a smaller one loses airflow and adds noise. Use rigid or smooth-wall metal duct where you can, keep the run short and straight, and always follow the fan’s installation sheet. The duct has to end outside, not in an attic.
What are sones, and what rating should I look for?
A sone is a loudness rating from HVI’s certified testing, and it is a linear scale: a 3 sone fan is about half as loud as a 6 sone fan. A 1.0 sone fan is about as loud as a refrigerator running. Buying guides suggest 1.0 sone or less for a fan that is not annoying and 2.0 or less as acceptable. These are typical figures, not code, and ratings are normally taken with the fan on a short or no duct. A quiet fan is also one that gets used.
How long should the fan run?
HVI recommends leaving the fan on for about 20 minutes after the bathroom is used, and a timer, a humidity-sensing control or a continuous low-speed fan at the 20 CFM code figure make that automatic. A fan that is correctly sized but turned off as soon as you leave does not clear the moisture, which is what causes mould and peeling paint.
Should a toilet in its own room have its own fan?
HVI says an enclosed toilet compartment should have its own fan. That is a separate fan of 50 CFM (or the code minimum), not something to add to the rest of the bathroom’s fixtures, so size the main bathroom and the toilet room separately.
Can I use this for a laundry room or a kitchen?
No. This page uses the HVI bathroom rules. Kitchen range hoods are sized differently, and the IRC kitchen minimum is 100 CFM on demand or 25 CFM continuous. For air changes per hour in any room, see the HVAC airflow (CFM) calculator.

Handy tools

  • Feet and Inches Calculator: Measured the bathroom as 5' 8 1/2"? It turns tape readings into the decimal feet the size fields take.