Bathroom Exhaust Fan Size Calculator (CFM)
A 10 × 8 ft bathroom is 80 sq ft, and the Home Ventilating Institute (HVI) method for a bathroom of 100 sq ft or less is 1 CFM per square foot, so it needs a fan of 80 CFM (never under 50 CFM). With 10 ft of duct and two elbows the airflow you actually get is less than the number on the box, so shop for about 90 CFM (a typical estimate). Over 100 sq ft the HVI method switches to fixtures: 50 CFM for each toilet, shower and tub and 100 CFM for a jetted tub. A ceiling over 8 ft raises the figure (room volume × 8 air changes per hour ÷ 60), and the International Residential Code floor is 50 CFM on demand or 20 CFM continuous.
Figures based on the sources listed belowUpdated How we calculate
80 CFM.
80 CFM
- HVI method: 80 CFM: 80 sq ft at 1 CFM per sq ft, minimum 50 CFM
- Fixture method: 100 CFM (2 toilet, shower or tub at 50 CFM each, jetted tubs at 100 CFM), used only above 100 sq ft
- Ceiling height check: 640 cu ft × 8 ACH ÷ 60 = 86 CFM, applied only over 8 ft
- Code minimum (IRC): 50 CFM on demand or 20 CFM continuous; this size meets it
- Fan rating to shop for: 90 CFM: 20 ft of equivalent duct costs about 10% of the airflow (typical estimate)
- Duct size: 4 in duct is enough for a 90 CFM fan (about 4 in is typical)
- Noise (sones): look for 1.0 sone or less for a quiet fan; 2.0 or less is common (typical, lower is quieter)
Shopping list
- Bathroom exhaust fan, 80 CFM
- Bathroom fan with humidity sensor
- Insulated flexible duct, 4 in
- Roof or wall vent cap, 4 in
- Foil duct tape (UL 181)
Your project
- Bathroom length × bathroom width: 10 × 8 ft
- Ceiling height: 8 ft
- Toilets: 1
- Showers: 1
- Bathtubs: 0
- Jetted tubs: 0
- Duct diameter: 4 in
- Duct run to outside: 10 ft
- Elbows in the duct: 2
Also pick up
- Bathroom exhaust fan, 80 CFM
- Bathroom fan with humidity sensor
- Insulated flexible duct, 4 in
- Roof or wall vent cap, 4 in
- Foil duct tape (UL 181)
Reopen this calculation: /calculators/bathroom-fan-size/?s=eyJyb29tIjp7Imxlbmd0aEZ0IjoxMCwid2lkdGhGdCI6OH0sImRlZHVjdGlvbnMiOltdLCJ3YXN0ZVBjdCI6MC4xLCJwYXJhbXMiOnsiY2VpbGluZ0Z0Ijo4LCJ0b2lsZXRzIjoxLCJzaG93ZXJzIjoxLCJ0dWJzIjowLCJqZXR0ZWRUdWJzIjowLCJkdWN0SW4iOjQsImR1Y3RMZW5ndGhGdCI6MTAsImVsYm93cyI6Mn19
Show diagram
Saved projects
No saved projects yet.
Fan size for common bathrooms
| Bathroom | Sq ft | HVI size | Rating to shop for |
|---|---|---|---|
| Powder room, 5 × 4 ft | 20 | 50 CFM | 60 CFM |
| Half bath, 6 × 5 ft | 30 | 50 CFM | 60 CFM |
| Guest bath, 8 × 5 ft | 40 | 50 CFM | 60 CFM |
| Full bath, 10 × 8 ft | 80 | 80 CFM | 90 CFM |
| Large bath, 10 × 10 ft | 100 | 100 CFM | 115 CFM |
Fan size by fixtures for bigger bathrooms
| Fixtures | Sq ft | Fixture total | Size used |
|---|---|---|---|
| Toilet and shower | 112 | 100 CFM | 100 CFM |
| Toilet, shower and tub | 140 | 150 CFM | 150 CFM |
| Toilet and shower, 12 × 12 ft | 144 | 100 CFM | 100 CFM |
| Toilet, shower and jetted tub | 168 | 200 CFM | 200 CFM |
| Two toilets, two showers and a jetted tub | 224 | 300 CFM | 300 CFM |
Fan size by ceiling height
| Bathroom | 8 ft ceiling | 9 ft ceiling | 10 ft ceiling | 12 ft ceiling |
|---|---|---|---|---|
| 5 × 8 ft | 50 CFM | 50 CFM | 54 CFM | 64 CFM |
| 8 × 10 ft | 80 CFM | 96 CFM | 107 CFM | 128 CFM |
| 10 × 10 ft | 100 CFM | 120 CFM | 134 CFM | 160 CFM |
Duct length derating (typical estimate)
| Equivalent duct length | Airflow lost | Rating to shop for, 80 CFM needed | Rating to shop for, 110 CFM needed |
|---|---|---|---|
| up to 10 ft | 0% | 80 CFM | 110 CFM |
| 11 to 25 ft | 10% | 90 CFM | 125 CFM |
| 26 to 50 ft | 20% | 100 CFM | 140 CFM |
| over 50 ft | 30% | 115 CFM | 160 CFM |
Duct size and noise (typical)
| Fan rating | Typical duct | Sones to look for |
|---|---|---|
| Up to 100 CFM | 4 in | 1.0 or less for quiet; 2.0 or less common |
| 101 to 200 CFM | 6 in | 1.0 or less for quiet; 2.0 or less common |
| Over 200 CFM | 8 in or larger | check the data sheet |
Local exhaust minimum for a bathroom (IRC)
| Operation | Minimum exhaust |
|---|---|
| Intermittent (on demand, a switch or timer) | 50 CFM |
| Continuous | 20 CFM |
Methodology & assumptions
This page sizes a bathroom exhaust fan in cubic feet per minute (CFM) in four steps. 1) The HVI method. The Home Ventilating Institute’s bathroom exhaust fan guidance gives a minimum of 50 CFM for a bathroom under 50 sq ft, 1 CFM per square foot of floor area for 50 to 100 sq ft, and, above 100 sq ft, the sum of the fixtures: 50 CFM for each toilet, shower and bathtub and 100 CFM for a jetted tub. HVI’s own pages are not worded identically about the 50 CFM floor (one chart applies it under 50 sq ft, other HVI text says 1 CFM per sq ft for rooms up to 100 sq ft, and the manufacturers that repeat it apply the 50 CFM minimum to all small baths), so this calculator takes the safe reading, 1 CFM per sq ft with a floor of 50 CFM for a room of up to 100 sq ft; the two readings agree from 50 sq ft up. HVI also says an enclosed toilet compartment should have its own fan and that higher rates are acceptable. A room over 100 sq ft with no fixtures entered falls back to 1 CFM per sq ft, so the answer is never blank. The fixture method is shown even when it is not used so you can compare. 2) Ceiling height. HVI’s guidance assumes a standard ceiling of about 8 ft. For a taller room this tool also works the volume method used in ventilation guides: CFM = length × width × ceiling height × air changes per hour ÷ 60, at 8 air changes per hour. The result is the larger of the HVI figure and the volume figure when the ceiling is over 8 ft; a 10 × 8 ft bathroom with a 10 ft ceiling is 800 cu ft, and 800 × 8 ÷ 60 is 107 CFM. The 8 air changes per hour is a common rule of thumb in ventilation guides rather than an HVI or code requirement; air changes per hour are covered on the HVAC airflow (CFM) page here. 3) Code. The International Residential Code (section M1505.4.4 in the 2021 edition, Table M1507.4 in the 2015 edition) lists a bathroom or toilet room at 50 CFM when the fan runs on demand (intermittent) or 20 CFM when it runs continuously, and the same figures are in ASHRAE 62.2. This is a minimum for the fan’s rated airflow, and the section and table numbers depend on the edition your area adopted, so check yours; local codes can be stricter. The HVI method gives at least 50 CFM, so it never falls under the on-demand code minimum. 4) Duct. A fan’s CFM on the box is measured at a test pressure (often 0.1 in. of water, with ENERGY STAR listings at 0.25 in.) while a real installation usually has more resistance, and the longer, smaller and more twisted the duct, the more airflow is lost. There is no standard derating table, so this tool uses its own typical estimate: add 5 ft of equivalent straight duct per 90° elbow to the run, then assume 0% loss up to 10 ft, 10% from 11 to 25 ft, 20% from 26 to 50 ft and 30% over 50 ft, and divide the needed CFM by what is left (rounded up to the next 5 CFM). Flexible duct, 3 in duct and a roof cap lose more. The only reliable figure is the fan’s own pressure-versus-airflow chart from its manufacturer, so use that for a long or complicated run. Duct size: retail and installer guides give about 4 in for a fan up to 100 CFM and 6 in for 100 to 200 CFM, which is how this tool flags a small duct; the fan’s installation sheet governs. Noise: fans are rated in sones (HVI-certified ratings), a scale where 1.0 sone is about a refrigerator running and a lower number is quieter; most buying guides suggest 1.0 sone or less for a quiet fan and 2.0 or less as acceptable, which are typical figures, not requirements. Humidity: HVI advises leaving the fan on for about 20 minutes after a shower. This is a sizing aid, not a ventilation design, and the fan’s ceiling or wall location, the make-up air and the local code are for you and your installer to settle. Figures are in CFM, so they do not change under the metric switch; the room fields convert between feet and metres.
- Home Ventilating Institute (HVI), “Bathroom Exhaust Fans” (hvi.org, Resources, Publications): the sizing chart, 50 CFM for under 50 sq ft, 1 CFM per square foot for 50 to 100 sq ft, and above 100 sq ft 50 CFM each for a toilet, shower and tub and 100 CFM for a jetted tub; enclosed toilets should have their own fan and higher rates are acceptable. Figures as quoted from the page; confirm against the original
- Home Ventilating Institute (HVI), “Bathroom Ventilation”: for bathrooms up to 100 sq ft recommends 1 CFM per square foot, and leaving the fan on for 20 minutes after use. Figures as quoted from the page; confirm against the original
- Fantech, “Bathroom ventilation” FAQ: restates the HVI rules, 1 CFM per square foot with a 50 CFM minimum for baths of 100 sq ft or less, plus 50 CFM for each toilet, shower or tub and 100 CFM for a jetted tub. A manufacturer page, figures as quoted from the page
- International Residential Code (2021), section M1505.4.4 (Table M1507.4 in the 2015 edition), local exhaust: bathroom or toilet room 50 CFM intermittent or 20 CFM continuous. Section and table numbers depend on the edition adopted; check your jurisdiction’s code. Found in a building-department guide and code-text excerpts, not in the ICC text itself
- ENERGY STAR, Ventilating Fans, key product criteria: bathroom and utility fans are certified for efficacy (2.8 CFM per watt for 10 to 89 CFM, 3.5 for 90 to 200 CFM, 4.0 for 201 to 500 CFM) and sound level, with airflow listed at 0.25 in. of water gauge, a more realistic installed pressure than the 0.1 in. on many box ratings. The sone limits in the current specification were not read, so this page does not quote them
- Panasonic, WhisperCeiling product literature and FAQ (iaq.na.panasonic.com): static pressure in typical installations is often above 0.25 in. of water, rated airflow falls as a 4 in duct gets longer, and 6 in duct is used on the higher-airflow models. The manufacturer’s pressure-versus-airflow chart for your fan is the real derating. Figures as quoted from the page; confirm against the original
- This site’s own assumptions, not from a published source: the 8 air changes per hour used for ceilings over 8 ft (a common ventilation-guide figure, not an HVI or code number), the duct derating bands (0, 10, 20 and 30% by equivalent length), 5 ft of equivalent duct per elbow, the duct size by CFM guide (about 4 in to 100 CFM, 6 in to 200 CFM, retail and installer guides) and the sone guidance (1.0 or less quiet, 2.0 or less typical). All are typical estimates: use your fan’s installation sheet and performance chart
How to size a bathroom exhaust fan
- Measure the bathroom. Measure the floor length and width in feet and multiply to get square feet, and note the ceiling height.
- Pick the HVI method. Up to 100 sq ft use 1 CFM per square foot with a minimum of 50 CFM. Over 100 sq ft add 50 CFM for each toilet, shower and tub and 100 CFM for a jetted tub.
- Check the ceiling. If the ceiling is over 8 ft, work length × width × height × 8 ÷ 60 and use that number if it is larger.
- Allow for the duct. Add about 5 ft of duct for each elbow to the run. A long, small or flexible duct loses airflow, so choose a fan rated higher than the CFM you need and check its pressure-versus-airflow chart.
- Choose duct size and noise. Use about 4 in duct to 100 CFM and 6 in above, and look for a fan of 1.0 sone or less. Check your local code for the 50 CFM on-demand or 20 CFM continuous minimum.
Worked examples
| Project | Result |
|---|---|
| 10 × 8 ft bathroom, 8 ft ceiling, 10 ft of 4 in duct with two elbows | 80 CFM (80 sq ft); shop for about 90 CFM |
| 8 × 5 ft guest bath | 50 CFM (40 sq ft, so the 50 CFM minimum applies) |
| 5 × 4 ft powder room | 50 CFM (20 sq ft, the 50 CFM minimum) |
| 10 × 10 ft bathroom, exactly 100 sq ft | 100 CFM (1 CFM per sq ft) |
| 14 × 10 ft master bath with a toilet, shower and tub | 150 CFM by the fixture method (140 sq ft) |
| 14 × 12 ft bath with a toilet, shower and jetted tub | 200 CFM by the fixture method (168 sq ft) |
| The 10 × 8 ft bathroom with a 10 ft ceiling | 107 CFM (800 cu ft × 8 air changes ÷ 60) |
| The same room with 30 ft of duct and three elbows | 80 CFM, shop for about 100 CFM (45 ft equivalent, 20% derating, a typical estimate); a 4 in duct is enough |
Frequently asked questions
- What size bathroom exhaust fan do I need?
- HVI’s rule for a bathroom of 100 sq ft or less is 1 CFM per square foot of floor area, with a minimum of 50 CFM. A 10 × 8 ft bathroom is 80 sq ft, so 80 CFM; a 5 × 4 ft powder room is 50 CFM because of the 50 CFM minimum. Over 100 sq ft, add up the fixtures (50 CFM per toilet, shower and tub, 100 for a jetted tub).
- How do I size a fan for a bathroom over 100 square feet?
- Use the fixture method: 50 CFM for each toilet, shower and bathtub and 100 CFM for a jetted tub. A 14 × 10 ft bathroom (140 sq ft) with a toilet, a shower and a tub is 150 CFM; a 14 × 12 ft room with a toilet, a shower and a jetted tub is 200 CFM. If you enter no fixtures, this calculator falls back to 1 CFM per sq ft (120 CFM for a 12 × 10 ft room), but the fixture count is the HVI method.
- Does the ceiling height change the CFM?
- HVI’s rule is written for a standard ceiling of about 8 ft. For a taller room, work the volume: length × width × height × 8 air changes per hour ÷ 60. A 10 × 8 ft room with a 10 ft ceiling is 800 cu ft, so 800 × 8 ÷ 60 gives 107 CFM, against 80 CFM at 8 ft. The calculator uses the larger of the two figures over 8 ft. The 8 air changes per hour is a common ventilation-guide rule of thumb, not an HVI or code figure.
- What does the building code require?
- The International Residential Code (section M1505.4.4 in the 2021 edition, Table M1507.4 in 2015) lists a bathroom or toilet room at 50 CFM for a fan that runs on demand or 20 CFM for one that runs continuously. ASHRAE 62.2 has the same local exhaust figures. These are minimums for the fan’s rated airflow; the HVI method gives at least 50 CFM, so it never falls under the on-demand figure. Codes are adopted and amended locally.
- What if my bathroom is exactly 100 square feet?
- Up to and including 100 sq ft the 1 CFM per square foot rule applies, so a 10 × 10 ft bathroom is 100 CFM. At 101 sq ft the HVI method switches to fixtures, and a toilet and shower give 100 CFM, which is about the same. The two rules meet around this size on purpose.
- Why does the calculator say to shop for a bigger fan than the CFM?
- A fan’s box rating is measured at a test pressure with little duct resistance. A longer run, more elbows, flexible duct or a small duct cut the airflow you actually get. There is no standard derating table, so this page uses its own typical estimate (0% to 10 ft of equivalent duct, 10% to 25 ft, 20% to 50 ft, 30% beyond), with each elbow counted as 5 ft. For the default 10 × 8 ft room with 10 ft of duct and two elbows, 80 CFM becomes about 90 CFM; with 30 ft of duct and three elbows (45 ft equivalent) it becomes 100 CFM. A fan’s own pressure-versus-airflow chart is the real answer.
- What duct size should I use for a bathroom fan?
- Retail and installer guides give about 4 in duct for a fan up to 100 CFM and 6 in for a 100 to 200 CFM fan, and many bigger fans are made for 6 in only. A bigger duct is never a mistake, since it lowers resistance; a smaller one loses airflow and adds noise. Use rigid or smooth-wall metal duct where you can, keep the run short and straight, and always follow the fan’s installation sheet. The duct has to end outside, not in an attic.
- What are sones, and what rating should I look for?
- A sone is a loudness rating from HVI’s certified testing, and it is a linear scale: a 3 sone fan is about half as loud as a 6 sone fan. A 1.0 sone fan is about as loud as a refrigerator running. Buying guides suggest 1.0 sone or less for a fan that is not annoying and 2.0 or less as acceptable. These are typical figures, not code, and ratings are normally taken with the fan on a short or no duct. A quiet fan is also one that gets used.
- How long should the fan run?
- HVI recommends leaving the fan on for about 20 minutes after the bathroom is used, and a timer, a humidity-sensing control or a continuous low-speed fan at the 20 CFM code figure make that automatic. A fan that is correctly sized but turned off as soon as you leave does not clear the moisture, which is what causes mould and peeling paint.
- Should a toilet in its own room have its own fan?
- HVI says an enclosed toilet compartment should have its own fan. That is a separate fan of 50 CFM (or the code minimum), not something to add to the rest of the bathroom’s fixtures, so size the main bathroom and the toilet room separately.
- Can I use this for a laundry room or a kitchen?
- No. This page uses the HVI bathroom rules. Kitchen range hoods are sized differently, and the IRC kitchen minimum is 100 CFM on demand or 25 CFM continuous. For air changes per hour in any room, see the HVAC airflow (CFM) calculator.