Attic Fan Size Calculator: CFM, Intake Vents and Whole-House Fans
A 40 × 30 ft attic floor is 1,200 sq ft, so a powered attic ventilator needs 840 CFM power attic fan: 1,200 sq ft × 0.7 CFM per sq ft = 840 CFM. Add 15% (0.805 CFM per sq ft, 966 CFM here) for dark shingles or a steep roof. The fan also needs intake: 1 sq ft of net free area per 300 CFM, which is 404 sq in of soffit vent for this attic. Choose the whole-house fan mode to size a fan from house volume instead: floor area × ceiling height × air changes per hour ÷ 60. These are rules of thumb: your fan’s manual has its own sizing chart and minimum intake.
Figures based on the sources listed belowUpdated How we calculate
840 CFM power attic fan.
840 CFM power attic fan
- Attic fan airflow: 840 CFM (0.7 CFM per sq ft of attic floor)
- Fans of the rating entered: 1 fan, at 1,250 CFM each
- Intake (soffit) vent area for the fan: 404 sq in (2.8 sq ft) of net free area, at 1 sq ft per 300 CFM
- Passive intake by code, for comparison: 576 sq in (4 sq ft) at 1/150, half of it low (attic ventilation calculator)
Shopping list
- Roof-mounted power attic fan
- Gable-mounted attic fan
- Whole-house fan
- Attic fan thermostat and humidistat
- Aluminum soffit vents
- Attic baffles (rafter vents)
Your project
- Floor length × floor width: 40 × 30 ft
- Fan type: Powered attic ventilator (roof or gable): size from the attic floor
- Roof: Light colour, moderate pitch: 0.7 CFM per sq ft
- CFM rating of the fan you plan to buy: 1,250 CFM
- Passive ventilation rule (for comparison): 1/150 of the attic floor area (base rule)
Also pick up
- Roof-mounted power attic fan
- Gable-mounted attic fan
- Whole-house fan
- Attic fan thermostat and humidistat
- Aluminum soffit vents
- Attic baffles (rafter vents)
Reopen this calculation: /calculators/attic-fan-size/?s=eyJyb29tIjp7Imxlbmd0aEZ0Ijo0MCwid2lkdGhGdCI6MzB9LCJkZWR1Y3Rpb25zIjpbXSwid2FzdGVQY3QiOjAuMSwicGFyYW1zIjp7Im1vZGUiOjEsInJvb2ZBZGRQY3QiOjAsImZhbkNmbSI6MTI1MCwiY2VpbGluZ0Z0Ijo4LCJhaXJDaGFuZ2VzIjoyMCwiY2ZtUGVyU3FGdE5mYSI6NzUwLCJyYXRpb0Rlbm9taW5hdG9yIjoxNTB9fQ
Show diagram
Saved projects
No saved projects yet.
Power attic fan CFM and intake by attic size
| Attic floor | CFM (0.7) | Intake, sq in | CFM (dark or steep) | Intake, sq in |
|---|---|---|---|---|
| 600 sq ft (30 × 20 ft) | 420 | 202 | 483 | 232 |
| 1,000 sq ft (40 × 25 ft) | 700 | 336 | 805 | 387 |
| 1,200 sq ft (40 × 30 ft) | 840 | 404 | 966 | 464 |
| 1,500 sq ft (50 × 30 ft) | 1,050 | 504 | 1,208 | 580 |
| 2,000 sq ft (50 × 40 ft) | 1,400 | 672 | 1,610 | 773 |
| 2,500 sq ft (50 × 50 ft) | 1,750 | 840 | 2,013 | 966 |
Whole-house fan CFM by house size and air changes
| House floor area | 15 changes | 20 changes | 30 changes | 60 changes | Attic vent, sq in (20) |
|---|---|---|---|---|---|
| 1,000 sq ft (40 × 25 ft) | 2,000 | 2,667 | 4,000 | 8,000 | 512 |
| 1,500 sq ft (50 × 30 ft) | 3,000 | 4,000 | 6,000 | 12,000 | 768 |
| 2,000 sq ft (50 × 40 ft) | 4,000 | 5,334 | 8,000 | 16,000 | 1,024 |
| 2,500 sq ft (50 × 50 ft) | 5,000 | 6,667 | 10,000 | 20,000 | 1,280 |
| 3,000 sq ft (60 × 50 ft) | 6,000 | 8,000 | 12,000 | 24,000 | 1,536 |
Intake and attic vent rules used here
| Fan | Vent rule | Where from |
|---|---|---|
| Powered attic ventilator | Intake: 1 sq ft of net free area per 300 CFM, at the soffit | HVI; matches GAF bulletin R174 |
| Powered attic ventilator, ERV5 (1,250 CFM) | Intake: 600 sq in minimum; up to 2,200 sq ft of attic floor | GAF Master Flow |
| Whole-house fan | Attic exhaust vents: 1 sq ft of net free area per 750 CFM | DOE Building America |
| Whole-house fan, cautious | Attic exhaust vents: 1 sq ft per 500 CFM | Field Controls (California Title 24) |
Methodology & assumptions
Powered attic ventilator: the Home Ventilating Institute (HVI) rule of thumb is attic floor area × 0.7 CFM per sq ft, with 15% added (0.805 CFM per sq ft) for a dark roof or a steep pitch. HVI’s own table gives 805 CFM for a 1,000 sq ft attic at the higher figure. Gibraltar, a maker of power vents, says the 0.7 comes from 10 to 12 air changes an hour in an attic about 8 ft tall at the ridge. Makers’ catalogues vary a little: some add 15% separately for a steep roof or a hot, humid climate, and one lists 0.84 for steep roofs. This tool applies a single 15% for a dark or steep roof, the figure HVI gives. The intake is 1 sq ft of net free area (NFA) for every 300 CFM of fan capacity, HVI’s guideline, which GAF’s bulletin on power attic vents matches: its 800 CFM example needs 384 sq in (800 ÷ 300 × 144) and its 1,250 CFM Master Flow ERV5 lists 600 sq in, a little more than the ratio gives (that is the maker’s figure for that fan, and your fan’s own minimum wins). HVI and GAF say to use soffit vents as the intake, never gable vents (rain and snow can be drawn in), and to keep other exhaust vents, such as a ridge vent, from short-circuiting the fan’s air; GAF says exhaust at the ridge should never exceed the soffit intake. The fan count divides the CFM by the rating you enter, rounded up. Fans are rated at free air, so actual flow against a real attic is lower. Whole-house fan: CFM = floor area × ceiling height × air changes per hour ÷ 60, which is the volume of the house times the changes an hour, per minute. The air-change figure is a choice, because sources differ widely: fan makers’ charts, such as QuietCool’s (2 to 3 CFM per sq ft, and a complete air change every 3 to 4 minutes), work out to 15 to 22 changes an hour on an 8 ft ceiling, while the U.S. DOE Building America guide says to pick a fan with a half to one house volume a minute, which is 30 to 60 changes an hour. This tool offers 15, 20, 30, 45 and 60 and defaults to 20. The attic has to exhaust what the fan pulls out of the house: 1 sq ft of NFA per 750 CFM is the common guideline (DOE Building America; QuietCool’s per-model minimums work out to about the same), and a Field Controls sheet cites 1 sq ft per 500 CFM from California Title 24, so that is offered as the cautious choice. Louvered vents and insect screens cut free area, so use the NFA printed on the vent. You also need open windows with at least as much area, and a fan’s manual lists its own minimum. For comparison the tool also shows the passive net free area the attic ventilation calculator gives for the same floor area (IRC R806.2: 1/150 of the floor area, or 1/300 where the exception is met; intake is half of it). That is the code-minimum figure for ordinary vents and is not changed here: a power fan does not replace it unless your building department says so. The shown comparison is only a check that you are not undersizing the low vents; install the larger of the fan’s need and the code figure. The metric toggle changes the lengths you enter; CFM and square inches are how fans and vents are rated, so they stay as they are. This is a sizing aid for ordinary houses, not an engineered ventilation design, and it does not look at the house’s moisture or air sealing: a fan in a leaky attic can pull conditioned air up through the ceiling, which is why some pros prefer sealing, insulating and passive vents.
- Home Ventilating Institute (HVI), Attic Ventilation: attic floor area × 0.7 CFM per sq ft, plus 15% (0.805) for dark shingles or a steep roof, with a table (805 CFM for 1,000 sq ft); 1 sq ft of inlet area for every 300 CFM of fan capacity; use soffit vents for intake, not gable vents. Figures as quoted from the page; confirm against the original
- GAF Technical Bulletin R174, Power Attic Vents and the Importance of Proper Attic Intake Ventilation: the more powerful the vent, the more intake needed (800 CFM needs 384 sq in, the 1,250 CFM ERV5 needs 600 sq in); exhaust at the ridge should not exceed the soffit intake. Figures as quoted from the page; confirm against the original
- GAF Master Flow ERV4, ERV5 and ERV6 product overview: 1,600, 2,200 and 2,800 sq ft maximum attic floor per vent, and 480, 600 and 720 sq in minimum intake net free area. Figures as quoted from the page; the 1,250 CFM rating of the ERV5QCT is from GAF’s ERV5QCT specifications (hvacquick.com copy)
- Gibraltar Building Products help centre, “When sizing power vent CFM, where does the 0.7 come from?”: 10 to 12 air changes an hour in an attic about 8 ft tall at the ridge. Figures as quoted from the page; confirm against the original
- U.S. Department of Energy, Building America whole-house fan guidance (publication 26291): multiply the gross floor area by the ceiling height (typically 8 ft) and choose a fan with one half to one times that figure in CFM at 0.1 in static pressure; 1 sq ft of net free vent area per 750 CFM is a sufficient guideline for attic venting. Figures as quoted from the guide and secondary sources; confirm against the full PDF
- QuietCool Stealth Pro whole-house fan listings (Sigler’s): each model’s CFM, recommended floor area at 2 to 3 CFM per sq ft, and minimum attic net free vent area (1.5X, 1,479 CFM, 1.98 sq ft; 2.5X, 2,541 CFM, 3.39 sq ft; 7.0X, 6,996 CFM, 9.33 sq ft). The retailer listing, not QuietCool’s own manual
- Field Controls VentCool whole-house fan product sheet: 1 sq ft of net free vent area per 500 CFM of fan capacity (citing California Title 24), or the fan maker’s own figures; louvered vents carry a 0.75 reduction factor
- This site’s own choices, not published rules: the 15, 20, 30, 45 and 60 air-change options (QuietCool’s one change every 3 to 4 minutes is about 15 to 20 an hour; DOE’s half to one volume a minute is 30 to 60) and the 20 default; the 1,250 CFM default fan rating (GAF Master Flow ERV5QCT, editable)
- International Residential Code (ICC), Section R806 Roof Ventilation: the passive net free area (1/150 or 1/300 of the attic floor) shown for comparison is the one in this site’s attic ventilation calculator, which has the full citation
How to size an attic fan
- Measure the attic floor. Multiply the length and width of the attic floor in feet to get square feet.
- Work out the CFM. Multiply by 0.7, or by 0.805 for dark shingles or a steep roof.
- Pick a fan. Choose a fan rated at or above that CFM, and check its chart for the largest attic it covers.
- Size the intake. Divide the CFM by 300 for the square feet of net free soffit vent area, and multiply by 144 for square inches.
- Check the passive vents. Compare with the code net free area from the attic ventilation calculator and install the larger of the two.
Worked examples
| Project | Result |
|---|---|
| 40 × 30 ft attic, light roof, power attic fan | 840 CFM power attic fan: intake 404 sq in, one 1,250 CFM fan (1,200 sq ft) |
| 40 × 30 ft attic, dark shingles | 966 CFM power attic fan: intake 464 sq in |
| 30 × 20 ft attic, light roof | 420 CFM power attic fan: intake 202 sq in |
| 50 × 40 ft attic, dark roof | 1,610 CFM power attic fan: intake 773 sq in, 2 fans of 1,250 CFM |
| 1,500 sq ft house, 8 ft ceilings, 20 air changes an hour, whole-house fan | 4,000 CFM whole-house fan: attic vent 768 sq in at 1 sq ft per 750 CFM |
| 1,500 sq ft house, 8 ft ceilings, 30 air changes an hour | 6,000 CFM whole-house fan: attic vent 1,152 sq in |
| 2,000 sq ft house, 9 ft ceilings, 30 air changes an hour | 9,000 CFM whole-house fan: attic vent 1,728 sq in |
| 1,500 sq ft house, 20 changes an hour, the 1 sq ft per 500 CFM rule | 4,000 CFM whole-house fan: attic vent 1,152 sq in |
Frequently asked questions
- What size attic fan do I need?
- HVI’s rule of thumb is 0.7 CFM per sq ft of attic floor. A 40 × 30 ft attic (1,200 sq ft) needs 840 CFM. For dark shingles or a steep roof, add 15%: 0.805 CFM per sq ft, or 966 CFM for the same attic. A 30 × 20 ft attic (600 sq ft) needs 420 CFM. Pick the next fan size up, and check the maker’s chart for the largest attic it covers.
- How much intake ventilation does an attic fan need?
- HVI says 1 sq ft of net free area for every 300 CFM of fan capacity. The 840 CFM example needs 404 sq in (2.81 sq ft), and it should be at the soffits, not at the gables. GAF’s own table for its 1,250 CFM fan lists 600 sq in, a little more than the ratio, so use the maker’s number when you have a particular fan. Too little intake overworks the motor, adds noise, and can pull air from the ridge vent instead of the soffit.
- How does this fit with the attic ventilation calculator?
- They answer different questions. The attic ventilation calculator gives the passive net free area the code asks for: for this attic at 1/150 that is 1,152 sq in in all, half of it low, which is 576 sq in of intake. A fan’s own intake need (404 sq in here) can be lower or higher than that. Install the larger of the two, and ask your building department whether a power fan can stand in for any exhaust vents, because the code figures are written for passive vents.
- Where does 0.7 CFM per sq ft come from?
- It is a rule of thumb from the power vent industry. Gibraltar says it comes from 10 to 12 air changes an hour in an attic about 8 ft high at the ridge. HVI publishes it as a minimum, and raises it 15% to 0.805 for dark shingles or a steep roof. It ignores the climate, the insulation and how leaky the ceiling is, so treat it as a starting point.
- Should I add 15% for a dark roof?
- HVI says to for dark shingles or a steep pitch. The 40 × 30 ft attic goes from 840 to 966 CFM, and a 50 × 40 ft attic from 1,400 to 1,610 CFM. Some makers add a further 15% for a hot, humid climate or use a different steep-roof figure, so go to the fan’s manual if you are close to a size limit.
- How many CFM does a whole-house fan need?
- Floor area × ceiling height × air changes per hour ÷ 60. A 1,500 sq ft house with 8 ft ceilings is 12,000 cu ft; at 20 changes an hour that is 4,000 CFM, and at 30 changes 6,000 CFM. The air changes you want are a choice: makers’ charts (2 to 3 CFM per sq ft, one change every 3 to 4 minutes) are 15 to 22 an hour, and the DOE Building America guide goes to 30 to 60. A 2,000 sq ft house with 9 ft ceilings at 30 changes is 9,000 CFM.
- How much attic vent area does a whole-house fan need?
- The common guideline is 1 sq ft of net free area per 750 CFM, which is 768 sq in for the 4,000 CFM example. Field Controls cites 1 sq ft per 500 CFM from California Title 24 (1,152 sq in). Louvered vents have less free area than their size, so use the NFA printed on the vent. You also need open windows that add up to at least that much, or the fan cannot move its rated air.
- Can a power attic fan replace ridge and soffit vents?
- Not by default. The code’s net free area figures are for passive vents. A fan works with the soffit intake, so the intake still has to be there, and a ridge vent beside a power fan can pull air from the ridge instead of the soffit. Some builders prefer to air-seal the ceiling and use passive vents alone, because a fan in a leaky attic can pull heated or cooled air up out of the house. Ask the building department and the fan maker.
- Is a whole-house fan the same as an attic fan?
- No. A powered attic ventilator sits in the roof or gable and exhausts only the attic, with the soffits as intake. A whole-house fan sits in the ceiling of the house, pulls air in through open windows and blows it into the attic, which then needs enough exhaust vent area. They are sized differently, which is why this tool has two modes.
- Is the ceiling fan calculator the same thing?
- No. A ceiling fan stirs the air in one room and is sized by blade span, not CFM. The ceiling fan size calculator covers that.